Installation
NOTES:
1. Connect Y1 terminal as
shown for proper operation.
2. Rinnai thermostats require a
"C" terminal connection as
shown.
3. If any of the original wire, as
supplied, must be replaced,
use the same type or
equivalent wire.
BLK
BLK
WHT
WHT
GND
115 Volt Fuse Disconnect
(Field Supplied)
Flow Sensor
(Packaged with Unit)
Electrical Connection to Control Box
1. Route the Air Handler power wires through aligned
holes in casing and Control Box and make field
wire connections in Control Box. Use best
practices for wire bushings, strain relief, etc.
Field wiring to the unit must be grounded and
conform to the National Electrical Code C22.1 Part
1 - latest edition. Use only UL listed conduit and
conduit connectors to connect supply wires to the
unit and provide appropriate grounding.
Grounding may also be accomplished by
grounding the control box per appropriate local
codes. Electric wires that are field installed shall
conform to the temperature limitation for 63° F
(35° C) rise wire when installed in accordance with
instructions. Refer to Table 3 in for specific air
handler electrical data.
2. Route and secure field ground wire to ground
screw on Control Box.
3. Connect line voltage leads as shown in Figure 13.
4. Reinstall cover to Control Box. Ensure that wires
are not pinched between cover and edge of
Control Box.
WARNING
Failure to follow this warning could result in a fire. Do
not use aluminum wire between the Hydronic Air
Handler and the disconnect switch. USE COPPER
WIRE ONLY.
3 Wire Heating Only
AIR HANDLER
Junction Box
Y1
Y2
L1
W
G
PCB
O
L2
R
C
Control Box
P3
24 Volt FS / WH Connector
FS
Figure 13:
Rinnai Corporation Hydronic Air Handler Manual
W
G
R
C
Y1
5 Wire
24 Volt Terminal Block
Field Wiring Diagram
24V Control System Connections to Unit's Printed-
Circuit Board (PCB):
Refer to Figures 25 through 27 for factory wiring
details. For low voltage connections between the unit
and the thermostat, use No. 18 AWG color-coded,
insulated (63° F / 35°C minimum) wires. (Refer to
Figures 16 through 19.)
Low Voltage Connections:
These units use a grounded 24 volt AC low voltage
circuit and require at least a 1 stage heating and a 1
stage cooling thermostat.
The "R" terminal is the hot terminal and the "C"
terminal is grounded.
"G" terminal is the fan input.
"Y1" terminal is the compressor Stage 1 input.
"Y2" terminal is the compressor Stage 2 input.
"O" terminal is the reversing valve input. The
reversing valve must be de-energized for heating
mode.
"R" terminal is 24 VAC hot.
"C" terminal is 24 VAC grounded.
"W" terminal is the heat input. This terminal also
energizes the emergency heat if configured for heat
pump.
Single Stage
Thermostat
(Available Accessory)
Field 115, 208 / 230 Volt Wiring
Field 24 Volt Wiring
Factory 24 Volt Wiring
Factory 115 Volt Wiring
208 / 230 Volt
Single Phase
Condensing Unit
Disconnect
(Field Supplied)
(Field Supplied)
GND
15