Selecting DHW heating
Auxiliary function (DHW)
As additional protection against bacteria, you can select "Pasteurisation".
The total cylinder content will be heated
at the first cylinder heating every Monday
to the "Set temp. 2" (see next chap-
ter).
In order that bacteria are also killed in the
DHW circulation line, the DHW circula-
tion pump (if installed) is started in addi-
tion to the cylinder heating.
Note
Temperatures above 60 °C can only be
achieved with an instantaneous heating
water heater in the heating flow or an
electric immersion heater EHE in the
DHW cylinder.
DHW
Set DHW temp.
Switching times DHW
DHW with e heating
Start optimisation
Stop optimisation
Pasteurisation
Set temp. 2
NO
Set temperature 2 (DHW)
You can set the "Set temp. 2" for the "Pasteurisation" (for killing bacteria, see
page 34) and for the "TEMP. 2" operating mode (see page 30). In the delivered
condition, the "Set temp. 2" is set to 60 °C.
34
Press the following keys:
1. "Device settings"
2. "Programming"
3. "DHW"
4. y/x for "Pasteurisation"
5. "YES/NO" to activate / deactivate
6. "BACK"
[1/0]
:
50.0
:
T
:
Yes
:
No
:
No
:
Yes
:
60.0
Back
the function
to confirm and exit the
menu