Version 4 - Cylinder Loading System With Several Vitocell 100-L In Series And Vitotrans 222 For Modulating Flow Temperatures - Viessmann Vitocell 100-H Technical Manual

Hide thumbs Also See for Vitocell 100-H:
Table of Contents

Advertisement

Installation — cylinder loading system
Version 4 — cylinder loading system with several Vitocell 100-L in series and Vitotrans 222 for modulating
flow temperatures
D
B
C
O
P
A
N
A Vitocell 100-L (here: 500 l capacity)
B DHW circulation pipe
C DHW circulation pump
D Draw-off points (DHW)
E Vitotrans 222 heat exchanger set with mixer assembly
F Vitotronic 200-H (type HK1B, type HK3B),
Vitotronic 100 (type GC1B, type GC4B),
Vitotronic 200 (type GW1B),
Vitotronic 300 (type GW2B, type GW4B) or
Vitotronic 300-K (type MW1B, type MW2B)
G Plate heat exchanger
Note
■ Establish cold water connection N with a tee with straight flow to
the cold water connection of the Vitocell-L. Always make the cold
water connection to the Vitotrans 222 as a tee branch.
■ In order to ensure a fault-free heating operation, make sure that the
residual head of cylinder loading pump L is greater than that of
DHW circulation pump C, giving due consideration to the pipework
pressure drop.
Connect in series if relatively continuous DHW demand can be expec-
ted, e.g. in large apartment buildings.
DHW heating
(cont.)
A
A
28
5
A
5
B
21 17 B
L
Q
G
H Heating water flow
K Heating water return
L Cylinder loading pump (secondary), highly efficient
N Common cold water connection with safety assembly to
DIN 1988
O Spring-loaded check valve
P Cylinder temperature sensor, top
(ON, terminals %A)
Q Cylinder temperature sensor, bottom
(OFF, terminals %B)
Note the max. draw-off rate when sizing for DHW heating. The max.
flow velocity to DIN 1988 should not be higher than 2 m/s (affects
stratification inside the DHW cylinder).
The benefits of connection in series are particularly evident when heat
exchangers with low output ratings are combined with large cylinder
capacities, as a large cylinder capacity makes it possible to use smaller
boilers or the input of district heating.
Due to the necessary high flow temperatures of the heat source, never
use a directly connected heating circuit without mixer.
For optimum operation, disable the DHW cylinder priority control at the
control unit.
F
A1
A1
52
20
H
K
M
E
VIESMANN
7
43