Installation — cylinder loading system
Version 3 — cylinder loading system with several Vitocell 100-L in parallel and Vitotrans 222 for constant
flow temperatures
A Vitocell 100-L (here: 500 l capacity)
B DHW circulation pipe
C DHW circulation pump
D Time switch
E Draw-off points (DHW)
F Junction box (on-site)
G Heating water flow
H Heating water return
Note
Establish cold water connection N with a tee with straight flow to the
cold water connection of the Vitocell-L. Always make the cold water
connection to the Vitotrans 222 as a tee branch.
7
VIESMANN
42
(cont.)
K Cylinder loading pump (secondary), highly efficient
L Plate heat exchanger
M Vitotrans 222 heat exchanger set
N Common cold water connection with safety assembly to
DIN 1988
O Upper temperature controller (ON)
P Lower temperature controller (OFF)
Q Spring-loaded check valve
Due to the necessary high flow temperatures of the heat source, never
use a directly connected heating circuit without mixer.
DHW heating