7.7.5

Underwriters Laboratories (UL)

Household Fire Warning System
Install at least one UL Listed four-wire latching type smoke detector rated to operate over the voltage
range of 11.2 VDC to 12.3 VDC. The maximum smoke detector load is 50 mA.
Install one UL Listed 85 dB audible device rated to operate over the range of 11.2 VDC to 12.3 VDC
as required for this application. Program the bell cut-off time for at least four minutes. Refer to
Programming Item 107 on page 37.
Install end-of-line resistor P/N: 47819 after last smoke detector.
Do not use a printer interface module.
Where two-wire addressable devices are used, do not place fire and intrusion devices on the same zone.
The system must be able to operate for at least 24 hr, and generate a full alarm output for at least 4 min
without AC power.
Household Burglar Alarm Unit
Install at least one UL Listed 85 dB audible device rated to operate over the voltage range of 11.2 VDC
to 12.3 VDC.
Install at least one IUI-EZ1 Control Center.
Program all zones to use end-of-line supervision.
Install intrusion initiating devices rated to operate over the voltage range of 11.2 VDC to 12.3 VDC.
Program all intrusion zones for audible notification.
Do not exceed 60 sec when programming Exit Delay. Refer to Programming Item 126 on page 38. Do
not exceed 45 sec when programming Entry Delay. Refer to Programming Item 127 on page 38.
Program the bell cut-off time for at least of four minutes. Refer to Programming Item 108 on page 37.
The system must be able to operate for at least 24 hr, and generate a full alarm output for at least 4 min
without AC power.
Commercial Burglary, Local
Use the D8108A Attack Resistant Enclosure with the D2402 Mounting Skirt.
Install at least one UL Listed 85 dB audible device rated to operate over the voltage range of 11.2 VDC
to 12.3 VDC. All wiring connections between the control panel and device must be in conduit.
Do not exceed 60 sec when programming Exit Delay. Refer to Programming Item 126 on page 38. Do
not exceed 60 sec when programming Entry Delay. Refer to Programming Item 127 on page 38.
Install a tamper switch to protect the enclosure door.
Set Programming Item 116 to 1 (Daily) to ensure the automatic test report is sent on a daily basis. Refer to
page 37.
Ensure that the integrated communicator is enabled (Programming Item 304 = 0; refer to page 45). Ensure
that the system can send low battery reports (Programming Item 358 = 1, 2, or 3; refer to page 45).
Install at least one IUI-EZ1 Control Center.
Program the bell cut-off time for at least 15 minutes. Refer to Programming Item 108 on page 37.
This system was not evaluated for Bank Safe and Vault applications.
The system must be able to operate for at least 24 hr, and generate a full alarm output for at least 15
min without AC power.
Commercial Burglary, Police Station Connected Protected Premises*
Refer to Commercial Burglary, Local for installation requirements.
Ensure that the integrated communicator is enabled (Programming Item 304 = 0; refer to page 45).
Commercial Burglary, Proprietary*
The integrated communicator is enabled (Programming Item 304 = 0; refer to page 45).
The system has one owner.
The system must be able to operate without AC power for at least 24 hours. The central station receiver
must be able to receive reports without AC power for at least 24 hours.
* Systems are approved for Encrypted Line Security when used in conjunction with the C900V2 Conettix IP
Dialer Capture Module and communicating over a packet-switched data network (PSDN).