call points must not have delayed fire alarm activation). The delay
time can be set (in EBLWin, System Properties) to 0-255 seconds.
Function for an analog or addressable smoke detector:
An alarm point has to be in "fire alarm state"
order to activate a fire alarm in the c.i.e. If an alarm point goes back
to "normal state" during the delay time, the delay time will be reset
and start again if/when the alarm point comes in "fire alarm state"
again.
Function for each addressable multipurpose I/O unit (3361) monitored
Input 0 (Z) and 8 zones expansion board (4580) input:
A zone in "fire alarm state" will be recorded in the c.i.e. but fire alarm
will not be activated. When the delay time has run out the zone will
be automatically reset and if it still is in "fire alarm state" a fire alarm
will now be activated in the c.i.e.
A delayed alarm is indicated in the control unit (c.i.e.) as follows:
The buzzer sounds like for pre-warning (0.8 / 5 sec.).
Information in the c.i.e. LCD, e.g. for a detector:
Delayed alarm detector ZZ/AA

Alarm Verification Facility

In some premises AVF can be used to avoid unwanted false alarms
(nuisance alarms). Note, this function is a violation to the EN54-2
standard.
This function is valid for any zone line input but only in the
Australian and New Zealand convention respectively.
In these conventions the function "Delayed alarm" (see above) is not
valid.
The function "Delayed" is selected in the dialog box for the zone line
input respectively.
Function: A zone in "fire alarm state"
but a fire alarm will not be activated. After 15 seconds the zone will
be automatically reset and if the zone comes in "fire alarm state" again
within 110 seconds, a fire alarm will be activated in EBL128, else
nothing will happen until the next time the zone is in "fire alarm state"
and so on.
102
Default is 30 seconds and a recommended delay time is < 30 seconds.
103
A zone with the AVF not selected would in this state activate a fire alarm
in EBL128.
102
EBL128 Planning Instructions V2.0.x
101
all the delay time, in
103
will be recorded in EBL128
102