Panasonic EBL128 Planning Instructions page 30

Fire alarm system
Hide thumbs Also See for EBL128:
Table of Contents

Advertisement

Panasonic Eco Solutions Nordic AB
MEW01622
Rev: -
 Type, i.e. output for Control, Alarm devices, etc.
 Output signal period (steady, pulse, delay, etc.)
 Supervised / Not supervised
 Logic, i.e. normally low (default) or normally high (24 V DC)
 Control expression (containing one or more trigger conditions)
One to five 33K resistors can be connected. When the connections are
finished, a calibration has to be performed. Calibration value has to
be in the range 4K7-50K. See also the EBL128 Operating Instructions
chapter "Calibration of supervised outputs (menu H5/A1)".
Voltage Output 0 (J1:1-2): max. 200 mA (Fuse F1).
(Brandmeldung)
Voltage Output 1 (J1:5-6): max. 200 mA (Fuse F2). "G" FSK öffnen
See also chapter "Programmable outputs", page 70.
Output 2 has to be programmed via EBLWin regarding:
 Type, i.e. output for Control, Alarm devices, etc.
 Output signal period (steady, pulse, delay, etc.)
 Logic, i.e. normally open (default) or normally closed.
 Control expression (containing one or more trigger conditions)
Output 2 (J1:11-12):
Normally closed (low resistance, 680R).
system (Löschanlage).
See also chapter "Programmable outputs", page 70.
Input 0-4 has to be programmed via EBLWin regarding:
 Type ("trigger condition")
 Supervised / Not supervised
 Logic, i.e. Normally open (high resistance, 3K3, when supervised)
or Normally closed (low resistance, 680R, when supervised)
 Additional information depending on selected type
Input 0 (J1:3-4):
Fire alarm routing equipment fault (Melder
quittung)
Input 1 (J1:7-8): German key cabinet (FSK rückmeldung)
Input 2 (J1:9-10): German key cabinet (FSK überwachung)
Input 3 (J1:13-14):
ausgelöst)
Input 4 (J1:15-16):
quittung)
See also chapter "Programmable inputs", page 63.
27
A normally high output can not be supervised. The supervision voltage is
1.5 – 3.7 V DC (depending on the number of supervision resistors) and the
polarity is reversed compared to an activated output.
28
Regarding system voltage, see chapter "Technical data", page 143.
EBL128 Planning Instructions V2.0.x
27
Normally open
(high resistance, 3K3) or
German extinguishing
German extinguishing system (Löschanlage
German extinguishing system (Löschanlage
28