Panasonic EBL128 Planning Instructions page 47

Fire alarm system
Hide thumbs Also See for EBL128:
Table of Contents

Advertisement

Panasonic Eco Solutions Nordic AB
MEW01622
Rev: -
NORMAL mode: Used for 3361 in EBL128.
2330 mode: Not used in EBL128.
2312 mode: Not used in EBL128.
NOTE! See also chapter "Limitations", page 174.
3364 Addressable 2 voltage outputs unit.
directly to the COM loop. External 24 V DC power supply is
required (via a 3366 unit or EBL128).
The unit has two programmable and supervised voltage outputs
(VO0-VO1), intended for alarm devices (e.g. sirens). An end-
of-line capacitor (470nF) is to be mounted in the last device
alt. a capacitor (470nF) in up to five alarm devices:
The unit also has a special voltage output (VO2) intended for
fire door closing only.
closing" and the controlling detectors have to be programmed.
The "fire door closing function" is described on page 92 and
besides that function, the output VO2 will also be powerless
approx. 30 sec. after:
- the "/Mains OK input" (terminal 8.) goes high, see below.
- the COM loop communication is interrupted = 3364 has no
connection / communication with EBL128.
The unit also has two inputs, i.e. one for power supply (24 V
DC) and one for "/Mains OK".
VO0: Normally low or high (set via EBLWin), 24 V DC, 1
51
A.
VO1: Normally low or high (set via EBLWin), 24 V DC, 1
51
A.
VO2: Normally high, 24 V DC, 1 A.
function.)
24 V DC:
From an external power supply (unit 3366 or
EBL128)
/Mains OK: From an external power supply unit (3366) when
the fire door closing function (ABDL) is to be used.
Normally low = The main power source
External power supply unit is okay.
Connections and examples, see drawings 128-21 & -28. The
unit's dimensions: (L x W x H) 90 x 70 x 32 mm. A plastic
protection cover is attached. The cover's dimensions: (L x W x
H) 129 x 73 x 45 mm. The unit is intended to be surface
mounted and for indoor use in dry premises. When required, the
unit can be mounted in a Waterproof box (IP66 / 67) 3362.
For more information, see the Technical Description and the
Product Leaflet.
The technical address is set with an Address setting tool 3314 /
4414 when the unit is powered. The unit has an address label
on which the programmed technical address is to be written.
The Address setting tool is also used for mode setting:
51
Cont. 1 A, during 10 ms 1.4 A.
EBL128 Planning Instructions V2.0.x
The unit is connected
The trigger condition "Fire door
51
(Fire door closing
45
(230 V AC) in the