Control expression

Each programmable output has to be given a control expression. It is
created by so called Boolean algebra.
Trigger conditions (see "Available functions"), logical "Operators"
(AND, OR, NOT) and parentheses are used to make a "control
expression" containing up to 40 trigger conditions. See also chapter
"Control expression examples" page 84.
A programmable output will be activated as long as its control
expression is true.
Figure 15.
In any output dialog box, click the right mouse
button in the large white field.
Disablement or Other to open a "Trigger conditions list".
Depending
on
the
arguments / data have to be entered. In the figure is the trigger
condition "General Fire Alarm" selected.

Trigger conditions

Some trigger conditions require additional information, see
information within parentheses (+nnnnn) after the trigger condition
respectively below.
The trigger conditions are divided into four groups as follows:
Alarm
Interlocking
Disablement
Other
The numbering of the trigger conditions is only for "the comments to
the trigger conditions" below:
EBL128 Planning Instructions V2.0.x