GE C70 Instruction Manual page 576

Capacitor bank protection and control system ur series
Hide thumbs Also See for C70:
Table of Contents

Advertisement

B.4 MEMORY MAPPING
Table B–10: MODBUS MEMORY MAP (Sheet 48 of 65)
ADDR
REGISTER NAME
ACD4
IEC 61850 Logical Node RBRFx Name Prefix (24 items)
AD1C
IEC 61850 Logical Node RPSBx Name Prefix
AD1F
IEC 61850 Logical Node RRECx Name Prefix (6 items)
AD31
IEC 61850 Logical Node MMXUx Name Prefix (6 items)
AD43
IEC 61850 Logical Node GGIOx Name Prefix (5 items)
B
AD52
IEC 61850 Logical Node RFLOx Name Prefix (5 items)
AD61
IEC 61850 Logical Node XCBRx Name Prefix (6 items)
AD73
IEC 61850 Logical Node PTRCx Name Prefix (6 items)
AD85
IEC 61850 Logical Node PDIFx Name Prefix (4 items)
AD91
IEC 61850 Logical Node MMXNx Name Prefix (37 items)
AE00
IEC 61850 Logical Node CSWIx Name Prefix (30 items)
AE5A
IEC 61850 Logical Node XSWIx Name Prefix (24 items)
IEC 61850 GGIO4 General Analog Configuration Settings (Read/Write)
AF00
Number of Analog Input Points in GGIO4
IEC 61850 GGIO4 Analog Input Points Configuration Settings (Read/Write Setting) (32 modules)
AF10
IEC 61850 GGIO4 Analog Input 1 Value
AF11
IEC 61850 GGIO4 Analog Input 1 Deadband
AF13
IEC 61850 GGIO4 Analog Input 1 Minimum
AF15
IEC 61850 GGIO4 Analog Input 1 Maximum
AF17
...Repeated for IEC 61850 GGIO4 Analog Input 2
AF1E
...Repeated for IEC 61850 GGIO4 Analog Input 3
AF25
...Repeated for IEC 61850 GGIO4 Analog Input 4
AF2C
...Repeated for IEC 61850 GGIO4 Analog Input 5
AF33
...Repeated for IEC 61850 GGIO4 Analog Input 6
AF3A
...Repeated for IEC 61850 GGIO4 Analog Input 7
AF41
...Repeated for IEC 61850 GGIO4 Analog Input 8
AF48
...Repeated for IEC 61850 GGIO4 Analog Input 9
AF4F
...Repeated for IEC 61850 GGIO4 Analog Input 10
AF56
...Repeated for IEC 61850 GGIO4 Analog Input 11
AF5D
...Repeated for IEC 61850 GGIO4 Analog Input 12
AF64
...Repeated for IEC 61850 GGIO4 Analog Input 13
AF6B
...Repeated for IEC 61850 GGIO4 Analog Input 14
AF72
...Repeated for IEC 61850 GGIO4 Analog Input 15
AF79
...Repeated for IEC 61850 GGIO4 Analog Input 16
AF80
...Repeated for IEC 61850 GGIO4 Analog Input 17
AF87
...Repeated for IEC 61850 GGIO4 Analog Input 18
AF8E
...Repeated for IEC 61850 GGIO4 Analog Input 19
AF95
...Repeated for IEC 61850 GGIO4 Analog Input 20
AF9C
...Repeated for IEC 61850 GGIO4 Analog Input 21
AFA3
...Repeated for IEC 61850 GGIO4 Analog Input 22
AFAA
...Repeated for IEC 61850 GGIO4 Analog Input 23
AFB1
...Repeated for IEC 61850 GGIO4 Analog Input 24
AFB8
...Repeated for IEC 61850 GGIO4 Analog Input 25
AFBF
...Repeated for IEC 61850 GGIO4 Analog Input 26
AFC6
...Repeated for IEC 61850 GGIO4 Analog Input 27
AFCD
...Repeated for IEC 61850 GGIO4 Analog Input 28
AFD4
...Repeated for IEC 61850 GGIO4 Analog Input 29
AFDB
...Repeated for IEC 61850 GGIO4 Analog Input 30
AFE2
...Repeated for IEC 61850 GGIO4 Analog Input 31
AFE9
...Repeated for IEC 61850 GGIO4 Analog Input 32
IEC 61850 GOOSE/GSSE Configuration (Read/Write Setting)
B01C
Default GOOSE/GSSE Update Time
B01D
IEC 61850 GSSE Function (GsEna)
B-56
0 to 65534
0 to 65534
0 to 65534
0 to 65534
0 to 65534
0 to 65534
0 to 65534
0 to 65534
0 to 65534
0 to 65534
0 to 65534
0 to 65534
0.001 to 100
–1000000000000 to
1000000000000
–1000000000000 to
1000000000000
C70 Capacitor Bank Protection and Control System
RANGE
UNITS
STEP
---
1
---
1
---
1
---
1
---
1
---
1
---
1
---
1
---
1
---
1
---
1
---
1
4 to 32
---
4
---
---
---
%
0.001
---
0.001
---
0.001
1 to 60
s
1
0 to 1
---
1
APPENDIX B
FORMAT
DEFAULT
F206
(none)
F206
(none)
F206
(none)
F206
(none)
F206
(none)
F206
(none)
F206
(none)
F206
(none)
F206
(none)
F206
(none)
F206
(none)
F206
(none)
F001
4
F600
0
F003
100000
F060
0
F060
1000000
F001
60
F102
1 (Enabled)
GE Multilin

Advertisement

Table of Contents
loading

Table of Contents