GE C70 Instruction Manual page 541

Capacitor bank protection and control system ur series
Hide thumbs Also See for C70:
Table of Contents

Advertisement

APPENDIX B
Table B–10: MODBUS MEMORY MAP (Sheet 13 of 65)
ADDR
REGISTER NAME
332C
Syslog Server IP Address
332E
Syslog Server Port Number
Security Supervisory (Read/Write Setting)
3331
Device Authentication Enable
3332
Supervisor Role Enable
3333
Lock Relay
3334
Factory Service Mode Enable
3335
Failed Authentication Alarm Enable
3336
Firmware Lock Alarm
3337
Settings Lock Alarm
3338
Bypass Access
333A
Serial Inactivity Timeout
Security Command (Read/Write Command)
3350
Operator Logoff
3351
Engineer Logoff
3352
Administrator Logoff
3353
Clear Security Data
Security Reserved Modbus Registers (Read/Write)
3360
Address 0x3360 reserved for serial login (20 items)
3374
Address 0x3374 reserved for serial logout
Security Reserved Modbus Registers (Read Only)
3375
Address 0x3374 reserved for serial logout
Event Recorder (Read Only)
3400
Events Since Last Clear
3402
Number of Available Events
3404
Event Recorder Last Cleared Date
Event Recorder Commands (Read/Write Command)
3406
Event Recorder Clear Command
Neutral Current Unbalance Commands and Actual Values (Read/Write Unless Noted) (3 modules)
3410
Neutral Current Unbalance Automatic Setting Function
3411
Neutral Current Unbalance Apply Magnitude
3412
Neutral Current Unbalance Apply Angle
3413
60N Apply Magnitude Actual Value (Read Only)
3415
60N Apply Angle Actual Value (Read Only)
3417
...Repeated for Neutral Current Unbalance 2
341E
...Repeated for Neutral Current Unbalance 3
Neutral Voltage Unbalance Commands and Actual Values (Read/Write Unless Noted) (3 modules)
3430
Neutral Voltage Unbalance Automatic Setting Function
3431
59NU XA/XB Ratio Actual Value (Read Only)
3433
Neutral Voltage Unbalance Auto-set XA/XB Ratio
3434
59NU XA/XC Ratio Actual Value (Read Only)
3436
Neutral Voltage Unbalance Auto-set XA/XC Ratio
3437
...Repeated for Neutral Voltage Unbalance 2
343E
...Repeated for Neutral Voltage Unbalance 3
Phase Current Unbalance Commands and Actual Values (Read/Write Unless Noted) (3 modules)
3450
Phase Current Unbalance Automatic Setting Function
3451
Phase Current Unbalance Ka Actual Value (Read Only)
3453
Phase Current Unbalance Auto-set Ka
3454
Phase Current Unbalance Kb Actual Value (Read Only)
3456
Phase Current Unbalance Auto-set Kb
3457
Phase Current Unbalance Kc Actual Value (Read Only)
3459
Phase Current Unbalance Auto-set Kc
345A
...Repeated for Phase Current Unbalance 2
3464
...Repeated for Phase Current Unbalance 3
GE Multilin
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 0.1500
0 to 9.9999
0 to 9.9999
–0.1000 to 0.1000
–0.1000 to 0.1000
–0.1000 to 0.1000
C70 Capacitor Bank Protection and Control System
RANGE
UNITS
STEP
---
1
1 to 65535
---
1
0 to 1
---
1
0 to 1
---
1
0 to 1
---
1
0 to 1
---
1
0 to 1
---
1
0 to 1
---
1
0 to 1
---
1
0 to 3
---
1
1 to 9999
---
1
0 to 1
---
1
0 to 1
---
1
0 to 1
---
1
0 to 1
---
1
0 to 9999
---
1
0 to 9999
---
1
0 to 5
---
1
---
1
---
1
---
1
0 to 1
---
1
0 to 2
---
1
0 to 1
---
1
0 to 1
---
1
---
0.0001
0 to 359
degrees
1
0 to 2
---
1
---
0.0001
0 to 1
---
1
---
0.0001
0 to 1
---
1
0 to 2
---
1
---
0.0001
0 to 1
---
1
---
0.0001
0 to 1
---
1
---
0.0001
0 to 1
---
1
B.4 MEMORY MAPPING
FORMAT
DEFAULT
F003
0
F001
514
F126
1 (Yes)
F102
0 (Disabled)
F102
0 (Disabled)
F102
0 (Disabled)
F102
1 (Enabled)
F102
1 (Enabled)
F102
1 (Enabled)
F628
0 (Disabled)
F001
1
F126
0 (No)
F126
0 (No)
F126
0 (No)
F126
0 (No)
F001
3
F001
3
F617
3 (Engineer)
F003
0
F003
0
F050
0
F126
0 (No)
F092
0 (Disabled)
F126
0 (No)
F126
0 (No)
F003
0
F003
0
F092
0 (Disabled)
F003
0
F126
0 (No)
F003
0
F126
0 (No)
F092
0 (Disabled)
F004
0
F126
0 (No)
F004
0
F126
0 (No)
F004
0
F126
0 (No)
B-21
B

Advertisement

Table of Contents
loading