GE C70 Instruction Manual page 432

Capacitor bank protection and control system ur series
Hide thumbs Also See for C70:
Table of Contents

Advertisement

7.1 COMMANDS
Description of problem: A link loss detection on an Ethernet port. The link loss is due to unplugging the cable or the
switch port being down.
How often the test is performed:
What to do: Check the connection.
AUTHENTICATION FAIL
Latched target message: No.
Description of problem: The number of failures threshold was exceeded.
What to do: Wait for the lockout interval and try to authenticate again.
FIRMWARE LOCK
Message: "Unauthorized firmware attempt"
Latched target message: No.
Description of problem: A firmware upgrade operation was attempted while the lock relay setting was enabled.
What to do: Ask the Supervisor to unlock the relay and try again.
SETTING LOCK
Message: "Unauthorized setting write"
Latched target message: No.
Description of problem: A setting write was attempted while the lock relay setting was enabled.
What to do: Ask the Supervisor to unlock the settings and try again.
SERVER UNAVAILABLE
7
Message: "An attempt to contact the Radius server has failed"
Latched target message: No.
Description of problem: The RADIUS authentication server is unavailable.
What to do: Verify network connectivity and try again.
d) WRONG TRANSCEIVER MESSAGES
Description: The type of SFP does not match the CPU type.
T-type CPU = All ports support fiber SFPs only
Type: minor
Target: latched
Message: "WRONG TRANSCEIVER"
A webpage "SFP Transceiver Information" is provided. This page displays the type of the SFP in it. This data is to be used
with the CPU type to know the cause of the problem.
e) SFP X MODULE FAIL MESSAGES
Description: A faulty SFP or unplugging the SFP would generate this self test.
7-14
C70 Capacitor Bank Protection and Control System
7 COMMANDS AND TARGETS
GE Multilin

Advertisement

Table of Contents
loading

Table of Contents