5.6 GROUPED ELEMENTS
a) MAIN MENU

PATH: SETTINGS
GROUPED ELEMENTS
 GROUND CURRENT
b) GROUND TIME OVERCURRENT (ANSI 51G, IEC PTOC)
5

PATH: SETTINGS
GROUPED ELEMENTS
 GROUND TOC1
This element can provide a desired time-delay operating characteristic versus the applied current or be used as a simple
definite time element. The ground current input value is the quantity measured by the ground input CT and is the funda-
mental phasor or RMS magnitude. Two methods of resetting operation are available: "Timed" and "Instantaneous" (see the
5-178
SETTING GROUP 1(6)
 GROUND TOC1
 GROUND TOC2
MESSAGE
 GROUND TOC6
MESSAGE
 GROUND IOC1
MESSAGE
 GROUND IOC2
MESSAGE
 GROUND IOC12
MESSAGE
SETTING GROUP 1(6)
GROUND TOC1
FUNCTION: Disabled
GROUND TOC1 SIGNAL
MESSAGE
SOURCE: SRC 1
GROUND TOC1
MESSAGE
INPUT: Phasor
GROUND TOC1
MESSAGE
PICKUP:
GROUND TOC1
MESSAGE
CURVE: IEEE Mod Inv
GROUND TOC1
MESSAGE
TD MULTIPLIER:
GROUND TOC1
MESSAGE
RESET: Instantaneous
GROUND TOC1 BLOCK:
MESSAGE
Off
GROUND TOC1
MESSAGE
TARGET: Self-reset
GROUND TOC1
MESSAGE
EVENTS: Disabled
C70 Capacitor Bank Protection and Control System

GROUND CURRENT
See page 5–178.
See page 5–178.
See page 5–178.
See page 5–179.
See page 5–179.
See page 5–179.

GROUND CURRENT
Range: Disabled, Enabled
Range: SRC 1, SRC 2, SRC 3, SRC 4, SRC 5, SRC 6
Range: Phasor, RMS
Range: 0.000 to 30.000 pu in steps of 0.001
1.000 pu
Range: see the Overcurrent Curve Types table
Range: 0.00 to 600.00 in steps of 0.01
1.00
Range: Instantaneous, Timed
Range: FlexLogic operand
Range: Self-reset, Latched, Disabled
Range: Disabled, Enabled