3. INSTALLATION DIAGRAM & ACCESSORIES
FLARED CONNECTIONS
This unit has fl ared connections on both indoor and outdoor sides.
Remove the outdoor units valve cover, then connect the pipe.
Refrigerant pipes are used to connect the indoor and outdoor units.
Be careful not to crush or bend the pipe in pipe bending.
Limits
Pipe length
Height difference
No. of bends
Refrigerant adjustment ... If pipe length exceeds 7 m, additional refrigerant
(R410A) charge is required.
(The outdoor unit is charged with refrigerant for pipe length up to 7 m.)
Up to 7 m
Pipe length
Exceeding 7 m
MS-GA80
Refrigerant to
MSH-GA71/80
be added
MS-GA60
MSH-GA60
ACCESSORIES
Check the following parts before installation.
<Indoor unit>
1 Installation plate
2 Installation plate fi xing screw 4 × 25 mm
3 Remote controller holder
4 Fixing screw for 3 3.5 × 16 mm (Black)
5 Battery (AAA) for remote controller
6 Wireless remote controller
7 Felt tape (Used for left or left-rear piping)
8 Air cleaning fi lter
PART TO BE PROVIDED AT YOUR SITE
Optional extension pipe
Indoor/outdoor unit connecting wire
A
(2-core 1.0 mm
2
-2.0 mm
2
)
B Extension pipe
C Wall hole sleeve
D Wall hole cover
Pipe fi xing band (The quantity depends on the
E
pipe length.)
Fixing screw for E 4 × 20 mm (The quantity
F
depends on the pipe length.)
G Piping tape
H Putty
I Drain hose (or soft PVC. hose, 15 mm inner dia.)
J Refrigeration oil
Power supply cord (See the table in 5
INDOOR/OUTDOOR WIRE CONNECTION
K
AND OUTDOOR POWER SUPPLY CORD
CONNECTION for the cord size.)
840 mm
Air outlet
500 mm
Note:
When operating the air conditioner in low outside temperature,
be sure to follow the instructions described below.
Never install the outdoor unit in a place where its air inlet/outlet
side may be exposed directly to wind.
To prevent exposure to wind, install the outdoor unit with its
air inlet side facing the wall.
To prevent exposure to wind, it is recommended to install a
baffl e board on the air outlet side of the outdoor unit.
MS-GA60
MS-GA80
MSH-GA60
MSH-GA71/80
25 m max.
30 m max.
10 m max.
15 m max.
10 max.
No additional charge is required.
Additional charge is required.
(Refer to the table below.)
55 g/m × (refrigerant piping length (m) -7)
55 g/m × (refrigerant piping length (m) -7)
20 g/m × (refrigerant piping length (m) -7)
1
7
1
2
2
1
1
2
1
1
8
1
1
2 to 5
2 to 5
1
1
1
1
1
4-10 mm × 21 mm slot
PIPING PREPARATION
1 Specifi cations
Use the refrigerant pipes that meet the following specifi cations.
Pipe
MS-GA60
MSH-GA60
For liquid
MS-GA80
MSH-GA71/80
For gas
• Use a copper pipe or a copper-alloy seamless pipe with a thickness of 0.8 mm (for
ø6.35, 9.52) or 1.0 mm (for ø15.88). Never use any pipe with a thickness less than
0.8 mm (for ø6.35, 9.52) or 1.0 mm (for ø15.88), as the pressure resistance is
insuffi cient.
2 Ensure that the 2 refrigerant pipes are insulated to prevent condensation.
3 Refrigerant pipe bending radius must be 100 mm or more.
Be sure to use the insulation of specifi ed thickness. Excessive thickness may cause
incorrect installation of the indoor unit and lack of thickness may cause dew drippage.
1
2
Note: Do not
obstruct the
air outlet.
6
3
4
5
A
Outside diameter
Insulation thickness
mm
mm
6.35
8
9.52
8
15.88
8
CAUTION
Decide the installation position using mark on the installation
plate indicating the indoor unit size as reference.
Piping can be directed towards rear,
right, downward, left or left-rear
directions.
Rear side
Right
D
Rear
H
Downward
C
7
B
G
F
E
Separate the 2 connecting pipes and
apply insulation individually.
E
F
8 mm thickness thermal insulation
plastic
When the piping is to be attached to
a wall containing metals (tin plated)
or metal netting, use a chemically
K
treated wooden piece 20 mm or
thicker between the wall and the piping
or wrap 7 to 8 turns of insulation vinyl
I
tape around the piping.
Units should be installed by licensed contractor according
to local code requirement.
Insulation material
Heat resisting
foam plastic 0.045
specifi c gravity
Be careful the
drain hose is not
raised.
Front
Left
Left-rear
Lock the catch.