OPTI-UPS DS1000B User Manual

OPTI-UPS DS1000B User Manual

Hide thumbs Also See for DS1000B:

Advertisement

User's Guide
Durable Series
Models DS1000B, 1500B, 2000B, 3000B
DS1000B-RM, 1500B-RM, 2000B-RM,
3000B-RM

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the DS1000B and is the answer not in the manual?

Questions and answers

Summary of Contents for OPTI-UPS DS1000B

  • Page 1 User’s Guide Durable Series Models DS1000B, 1500B, 2000B, 3000B DS1000B-RM, 1500B-RM, 2000B-RM, 3000B-RM...
  • Page 2 LIMITED WARRANTY What the warranty covers: For your records We warrant this product to be free from defects in material and workmanship during the warranty period. If a product proves to be defective in material or The serial number of your UPS is on the rear panel. You should note the serial workmanship during the warranty period, we will at our sole option repair or number in the space provided below.
  • Page 3 Opti Australia reserves the right to request proof of purchase upon any warranty claim. Limitation of implied warranties: Life Support: THERE ARE NO WARRANTIES, EXPRESS OR IMPLIED, WHICH EXTEND BEYOND THE DESCRIPTION CONTAINED HEREIN INCLUDING THE IMPLIED We do not recommend the use of our UPS products for life support equipment or WARRANTY OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR direct care where failure of a UPS product could cause failure of, or diminished PURPOSE.
  • Page 4: Table Of Contents

    TABLE OF CONTENTS EMC Statements 1. Introduction ...................3 FCC Part 15 2. System description................3 2.1 General description..................3 NOTICE: Pursuant to section 15 of the FCC rules, this product has been tested and thereby complies to the conditions of a Class B (1000VA-2000VA) and Class A (3000VA) digital 2.2 System Configuration ..................5 device, which have been established for offering sufficient protection against dangerous 3.
  • Page 5: Important Safety Instructions

    IMPORTANT SAFETY The instructions contained within this safety manual are deemed important and should be closely followed at all times during installation and follow-up maintenance of the UPS and INSTRUCTIONS batteries. SAVE THESE INSTRUCTIONS CAUTION ● CAUTION (UPS Having Internal Batteries): Risk of electric shock – Hazardous live The unit has a dangerous amount of voltage.
  • Page 6: Introduction

    DC power is converted to AC in the inverter passing it on to the load. 1. Introduction Power is maintained from the battery during a power failure. The information provided in this manual covers single phase 1000 – 3000 VA, uninterruptible power systems, their basic functions, operating procedures, and emergency The converter increases voltage appropriately for the inverter.
  • Page 7: System Configuration

    sends any forewarnings if replacement is needed. Otherwise every 30 days of normal mode 3. Safety Information operation, a battery discharge test is performed and any problems reported on the LCD display. Information presented here is vital to all personnel and please also read the UPS safety manual.
  • Page 8: Storage

    4. Storage Installations with accessories of “Vertical” and “Wall-mounted” types: Please install the vertical and wall-mounted types of units according to the following Please adhere to the following instructions if the UPS is not installed immediately: illustration. Store the equipment as is in its original packing and shipping carton Note: The product diagrams below are used for illustrating installation procedure only.
  • Page 9: Rear Panel Views

    5.2 Rear panel views Installation with accessories of “Rack-mounted” types: Please install the types of units according to the following illustration. 1KVA - 1.5KVA Rear Panel SMART SLOT RS232 Note: The product diagrams below are used for illustrating installation procedure only. (OPTIONAL) They may not be exactly the same with the product you purchased.
  • Page 10 2KVA-3KVA Rear Panel RM (1U) 1KVA Rear Panel SMART SLOT EPO RS232 CIRCUIT SMART SLOT (OPTIONAL) BREAKER (OPTIONAL) RS232 DATA LINE PROTECTION BATTERY BACKUP OUTLETS EXTENDED INPUT BATTERY (100/110/120V) CONNECTOR CIRCUIT BREAKER CIRCUIT SMART SLOT BREAKER RS232 BATTERY BACKUP OUTLETS INPUT (220/230/240V) CIRCUIT...
  • Page 11: Connection To Mains And Loads (1000 - 3000 Va)

    RM (2U) 2K-3KVA Rear Panel 5.3 Connection to mains and loads (1000 - 3000 VA) The accessories with UPS BATTERY BACKUP DATA LINE CIRCUIT BREAKER PROTECTION RS232 OUTLETS SMART SLOT 100/110/120V UPS Accessory User’s Guide x 1 Input Power Cord x 1 Telephone Line x 1 RS232 x 1 1000 –...
  • Page 12: Default Settings At The Factory

    6. Computer and Alarm connections At the back of the UPS is an interface allowing direct communication with your computer system, the location of which can be found in figure 2. There is a RS232 serial data interface, one USB data interface and an emergency power off switch supplied. However, the RS232 port cannot be used when the USB interface is in use.
  • Page 13: Epo Port (Emergency Power Off)

    7. User’s guide to operations USB port Necessary information for operation of the unit is covered in this chapter. Connecting the UPS to your computer is accomplished through the USB port on the back of Normally the UPS runs automatically, but on those few occasions such as just your computer.
  • Page 14: Control Panel Functions

    (b) If no button is pressed within 10 seconds, it will return to original status. Status of the UPS, measurements and alarms are all indicated on the LCD screen. 3. “FUNC” is a Function button. Each function can be enabled by pressing this button. (a).
  • Page 15 UPS configurations 1. Various settings that have been chosen are shown in the UPS setting display. Factory Settings Explanation Selection display default 2. To enter configuration mode, press the “FUNC” button for one second. The first 208/220/230/240 V 230V O/P V configuration parameter will be shown on the LCD display.
  • Page 16: Interpreting Ups Messages

    7.5 Trouble shooting Manual test of the UPS Displayed on LCD Audible Alarm Alarm Description What You Should Do Manual UPS or Manual Battery tests can be conducted from the UPS configuration as well Output Overload Two Beeps per The UPS is overloaded (in Shut off the least important and are functional even when the UPS is not charging the battery.
  • Page 17: Maintenance

    8. Maintenance With a minimal amount of maintenance, you can expect the UPS to function normally. However, the batteries may need to be changed every 2 – 3 years as it reaches the end of its service life. The most critical issues for the reliability of the UPS are environmental issues. Ensure that the temperature and humidity are always according to specifications and keep the area around the unit clean and dust free.
  • Page 18: Warranty

    Input Voltage range: 120/140/160 VAC-276 VAC 9. Warranty Frequency: 50/60 Hz. Auto selection Warranty on this product is valid against defects in material and workmanship Frequency window from mains 45-65 Hz for a period of 24 months from its original date of purchase. Synchronization window ±...
  • Page 19: Power Range 1000-3000 Va (100/110/120V 19" Rack-Mount Model)

    Frequency regulation ± 0.25 Hz (battery or free running mode) STANDARDS * 60V at 40% load, 70V at 70%, 80V at 100%. Safety: EN50091-1-1 ENVIRONMENTAL Emissions: EN50091-2 class B Immunity: EN50091-2 Ambient temperature: +0 °C to +40 °C Recommended temperature: +15 °C to +25 °C 100/110/120V Model Storage temperature:...
  • Page 20: Battery Packs

    10.5 Battery Packs 220/230/240V Model OUTPUT Tower Battery Packs 1000VA/700W 1500VA/1050W 2000VA/1400W 3000VA/2100W POWER 1000 VA 1500 VA 2000 VA 3000 VA Connection Input IEC 320 (10A) IEC 320 (10A) IEC 320 (10A) IEC 320 (16A) Battery type Lead-acid 7.2 Ah / Lead-acid 9 Ah / Lead-acid 7.2 Ah / Lead-acid 34 W /...