closed and two minutes later, the change valve is closed. The indoor blower fan is running at the set speed.
Restart up six minutes later; if the above situations appear again within ten minutes, all the outputs are shut
down through the electric control board and display failure.
●
When you press turbo button of remote, the air conditioner enter turbo running, compressor ,outdoor blower
fan and four-way valve turn on all along, indoor blower fan run at high speed and it must meet start
condition, turbo indication is light.
●
After the compressor runs five minutes, the lamp flashes 4 times per six seconds or display E4 if the
temperature of indoor coil pips is less than 30℃ (heating) in the continuous 20 minutes. The controller will
automatically shut down if the temperature of indoor coil pips is less than 30℃ in another continuous 20
minutes, that is the abnormality protection of outdoor units and the indicator lamp keeps its former state of
flashing.