HARBOR POINT WALL SPLIT DUCTLESS SYSTEMS
Refrigerant Line Set Piping
Interconnecting line set between the
outdoor unit and the indoor unit, must have
both refrigerant lines insulated as the
expansion device is located in the outdoor
unit.
Gently bend the line set stubs from the
in- door unit to the desired location.
Using 2 x 10"/12" Crescent wrenches
remove the flare nuts from the indoor
unit line stubs.
The indoor unit is filled with a dry
gas, check for release of this to ensure
that no leaks are present. Use a small
amount of vacuum pump oil on the male
flare threads to ease installation.
remove line
set cover
Indoor Unit
IR HIGH WALL DUCTLESS SPLIT SYSTEMS
OUTDOOR UNIT INSTALLATION
Outdoor
Unit
Connect the line set to the stubs. Using
the 2 wrenches, 1 on the male and 1 on
the female tighten the flare nuts. Run the
line set to the outdoor unit, avoid tight
bends and kinking the lines.
If line set length is in excess of that re-
quired, cut line set and re-flare or coil ex-
cess vertically to facilitate oil return to the
compressor.
Service port
9,000/12,000 Btu model shown.
(18,000/24,000 Btu models have
an additional liquid line port.)
Install the line set on the
indoor unit stubs.
10
Gas line service valve
Line set connections
under the GRAY
caps.
Liquid line service valve