Check code display list (Outdoor unit)
[SMMS-i interface detects error: Main example]
Check code display
Outdoor 7-segment
Auxiliary code
No. of indoor units which received signal
E06
normally
E07
E08
Duplicated indoor unit number
01: Indoor/Outdoor communication
E12
02: Communication between Outdoor units
E15
00: Capacity over
E16
01 ~ : No. of connected units
00: No center outdoor unit
E19
02: 2 or more center outdoor units
01: Connected to outdoor of other line
E20
02: Connected to indoor of other line
00: Duplicated header units
E21
02: No header unit
E22
E23
E25
E26
Receive error of outdoor address
E28
Detected outdoor unit number
A3-IPDU
A3-IPDU
FAN
FAN
IPDU
IPDU
1
2
3
1
2
3
01
¡
0A
¡
¡
¡
¡ ¡
¡
02
0B
¡ ¡
¡
¡
03
0C
E31
04
¡
0D
¡
¡
¡
¡
¡
¡ ¡
¡
05
0E
¡ ¡
¡ ¡ ¡
¡
06
0F
07
¡ ¡ ¡
¡
¡
08
mark:
Error position.
¡
¡
09
F04
F05
01: TE1
F06
02: TE2
F07
F08
F11
F12
F15
F16
F22
F23
F24
F31
Sensor lamp display
Block display
TCC-LINK central &
remote controllers
Operation Timer Ready Flash
l
l
¥
E06
l
l
¥
(E04)
l
l
¥
(E08)
l
l
¥
E12
l
l
¥
E15
l
l
¥
E16
l
l
¥
E19
l
l
¥
E20
l
l
¥
E21
l
l
¥
E22
l
l
¥
E23
l
l
¥
E25
l
l
¥
E26
l
l
¥
E28
l
l
¥
E31
¥
¥
¡
F04
A
¥
¥
¡
F05
A
¥
¥
¡
F06
A
¥
¥
¡
F07
A
¥
¥
¡
F08
A
F11
¥
¥
¡
F12
A
¥
¥
¡
F15
A
¥
¥
¡
F16
A
¥
¥
¡
F22
A
¥
¥
¡
F23
A
F24
¥
¥
¡
A
¥
¥
¡
F31
S
(∗) ¡: Goes on, ¥: Flashes, l: Goes off
A (Alternate)
S (Simultaneously) : Two LED flash simultaneously when there are two flashing LED.
Main defective position
Decrease of quantity of indoor units
No communication from indoor unit
(Decrease of connected indoor units)
Indoor/Outdoor communication circuit error
Signal cannot be sent to indoor unit.
(→There is no communication from outdoor unit.)
Duplicated indoor address
There are multiple indoor units having the same address.
(Detected also at indoor unit side)
Automatic address start error
Automatic indoor address operation while setting automatic address of other system
Outdoor automatic address operation while setting automatic indoor address
There is none during auto addressing.
There is no signal receiving from outdoor unit during automatic addressing.
No. of connected indoor units:
Total capacity of indoor units exceeded (total capacity of outdoor units × 135%)
Over capacity
No. of center outdoor units error
There is no center outdoor unit or there are 2 or more outdoor units in 1 line.
Connected to other line during automatic
Indoor unit of other line was detected during automatic address is been setting.
addressing
Header heat unit quantity error
There is no header heat unit in the system, or there are multiple header units.
Decrease of heat unit quantity
No communication from heat unit (Decrease of connected heat units)
Send error communication between
Sending to other outdoor is unavailable.
outdoor units
Duplicated terminal outdoor address setting
Manually set outdoor address was duplicated.
Decrease of connected outdoor units
No communication from terminal outdoor unit
(Decrease of connected terminal outdoor units)
Terminal outdoor error
Center outdoor unit detected terminal outdoor unit error.
(For terminal outdoor unit, details are displayed.)
IPDU communication error
No communication of each IPDU (P .C. board) in inverter box
Outdoor discharge temp. sensor (TD1) error
Open/Short of outdoor discharge temp. sensor (TD1) was detected.
Outdoor discharge temp. sensor (TD2) error
Open/Short of outdoor discharge temp. sensor (TD2) was detected.
Outdoor heat exchanger temp. sensor
Open/Short of heat exchanger temp. sensor (TE1, TE2) was detected.
(TE1, TE2) error
Outdoor liquid temp. sensor (TL) error
Open/Short of outdoor liquid temp. sensor (TL) was detected.
Outdoor outer air temp. sensor (TO) error
Open/Short of outer air temp. sensor (TO) was detected.
Outdoor suction temp. sensor (TS1) error
Open/Short of outdoor suction temp. sensor (TS1) was detected.
Outdoor temp. sensor (TE1, TL) miswiring
Miswiring by temp. sensor (TE1, TL) was detected.
Outdoor pressure sensor (Pd, Ps) miswiring
Miswiring by outdoor pressure sensor (Pd, Ps) was detected.
Outdoor discharge temp. sensor (TD3) error
Open/Short of outdoor discharge temp. sensor (TD3) was detected.
Low pressure (Ps) sensor error
Output voltage of low pressure (Ps) sensor detected 0.
High pressure (Pd) sensor error
Output voltage of high pressure (Pd) sensor detected 0 or error value was
detected during stop of compressor.
Outdoor EEPROM error
Outdoor EEPROM error
(Center unit stops alarm and terminal unit continues operation.).
: Flashing condition is alternate when there are two flashing LED.