Internal Battery Pack; End Of Discharge Voltages; Mechanical Requirements; Audible Noise - Orion SCR2 User Manual And Instructions

6kva on-line rt ups
Table of Contents

Advertisement

Line Mode
Overload Capability
Inverter overload
for 10 seconds minimum, then transfer to bypass
Inverter overload
for 2 seconds minimum, then transfer to bypass
Inverter overload
for 96 msec minimum, then transfer to bypass
6.3 Internal Battery Pack (all parameters are defined
at 25 degC)
Rating / Type
Voltage
Back-up Time (at 25 degC)
Extended Battery Capability
Recharge Time (internal
Six hours to 90% capacity after discharged into full load
battery)

6.4 End of Discharge Voltages

The end of discharge shutdown voltage will be based on the total runtime.
Discharging time  50 minutes,
50minutes < Discharging time  4Hrs,
4Hrs < Discharging time
6.5 Mechanical Requirements (generally 4U UPS with
2U VBATT for 19 inch rack)
Model
Width (tower) /Height (rack)
176 mm (6.93 in)
Depth (incl. handles)
592 mm (20.55 in)
Height (tower) /Width (rack)
430 mm (16.93 in)
The 4U UPS will use one UPS bezel and one battery bezel from the 2U UPS
models. The 2U battery cabinet will use one 2U battery bezels
 88 % AC-AC, minimum
112 to 130 %,  10 %;
131 to 200 %,  10 %;
> 201 %,  10 %;
Model: 6kva 120v/240v and External Battery
Cabinets
12V / 9AH
144Vdc nominal, 12 x 12V
5 minutes minimum at full rated load
Yes, through safe connector on rear of UPS
at nominal input voltage
Batt Vcutoff = 9.6V/pcs
Batt Vcutoff = 10V/pcs
Batt Vcutoff = 10.5V/pcs
6 KVA UPS 4U
External Battery 2U
87 mm (6.93 in)
592 mm (20.55 in)
430 mm (16.93 in)
16

6.6 Audible Noise

UPS Model
6000 VA
Environmental Requirements
The UPS will be capable of withstanding the following environmental conditions:
** Ambient Temperature Range
Operating:
0 degC to +40 degC for altitude 0 to 1500 meter above sea level
Non-operating: -15 degC to +50 degC
** Humidity:
0% to 95% non-condensing
Orion Power Systems Service and Technical Support
If you have any problems or questions with the UPS, call your local distributor or
Orion Power Systems technical support at the following telephone number :
In the United States: 1-877-385-1654
Please have the following information ready when you call:
- Model number and Serial number
- Description of failure or problem
- Date of failure or problem
- Customer contact information and return address
If repair is necessary, you will be given a Returned Material Authorization
(RMA) number. The RMA number must appear on the outside of the box
and on the Bill Of Lading. Original packaging should be used if available.
Systems that get damaged in transit as a result of improper packaging are
not covered under warranty. A replacement or repair unit will be shipped,
freight prepaid for all units under warranty.
NOTE:
For critical applications, immediate replacement may be available.
Noise Level
55 dBA Max
17