Safety Precautions - Orion SCR2 User Manual And Instructions

6kva on-line rt ups
Table of Contents

Advertisement

1.2.2 Mechanical specifications
Dimensions (mm)
Model
W×D×H
NO.
Online 6kva
176×615×430
RT 120v

1.3 Safety Precautions

Detailed safety regulations
All the safety regulations described in this manual shall be strictly observed during
the installation and maintenance of the UPS and battery assembly.
Note:
The UPS unit contains a battery pack which is very heavy; in order to prevent
the rack from falling over, the UPS unit shall be positioned as low as possible
in the rack.
Connect the UPS to a socket furnished with a circuit breaker or fuse
protection and capable of sustaining a current of at least 30A.
To ensure normal operation, this device shall not be used to power electric
drills, vacuum cleaners or laser printers, for which transient starting current is
high.
The UPS contains high voltage; in case of any problem, please consult a
professional or contact the service center for assistance to prevent any injury.
The UPS carries the power of the battery pack; the output may carry an
output voltage even if the UPS is disconnected from the power mains.
The rated voltage of the internal battery pack is 144VDC.
Grounding wire – a non-loading PVC wire that is green or green with narrow
yellow strips.
The grounding wire depicted above denotes the connection wire that
connects the metal casing of the device to the ground.
The maintenance and replacement of the battery pack shall be carried out by
a trained UPS professional. No other personnel shall be allowed to
manipulate the UPS.
When replacing the battery, observe the principle of consistency in the
quantity, brand and model number. In case of any problem resulting from the
customer using batteries other than that approved, the customer shall be held
responsible.
Weight (kg)
Net weight
35
31
35
4
It is strictly forbidden to expose the battery or battery pack to fire, or
explosion and injury may occur.
Never dismantle or damage the battery arbitrarily, or else the battery fluid
may spill out. The battery fluid is highly corrosive; it may cause severe injury
to the skin and eyes if touched.
Shorting electrodes of the battery will cause risks of high voltage and high
electric current.
Placing magnetic objects upon the UPS may cause data loss or damage.
In order to secure safe and continued operation, the
user must observe the regulations for using the UPS
correctly and the following precautions:
Do NOT open the outer cover of the UPS.
Avoid placing the UPS in an environment of high temperature and humidity.
Do NOT pour any liquid or poke any object into the UPS.
Do keep the venting slots in the front, rear and sides unclogged.
Avoid exposing the UPS to direct sunshine and avoid placing it near a heat
source.
High-voltage Risks:
Note: High-voltage will be present between a battery electrode and the
ground if the battery circuitry and input voltage are not isolated. Check any
electrode for high-voltage before touching it.
Note: Even if the UPS is disconnected from the power mains, internal parts of
the UPS are still connected to the battery pack. Therefore a potential risk
exists. Make sure the battery jumpers are disconnected before performing
any maintenance or repair.
Warning: Batteries will age with the time. When aging occurs, consult
professionals for regular replacement or treatment, or the battery fluid may
leak, causing fire or other hazards. We suggest regular maintenance to
check the batteries once a year.
Note: Batteries tend to age and gradually lose their capacity when used at the
normal temperature (approx. 25°C). A normal lifespan is 2-3 years. If batteries are
used with frequent cycles of charging and discharging, the lifespan will be further
shortened.