7

WIRING DIAGRAM

PVA-A30, 36, 42AA4
1
CN3C SW1
(BLUE)
3
SW2
CN90
OFF
1
2
3
ON
SW5
4
5
6
7
8
9
LED3
(GREEN)
CNF
CN44 CN4F
1
2
3
4
12 3 4 5 6 7 8 9
CN1
LED1
BZ1
RU
SW1
SW2
W.B.
OPTIONAL PARTS
TH2
TH5
SYMBOL EXPLANATION
SYMBOL
NAME
I.B.
INDOOR CONTROLLER BOARD
CN24-1
CONNECTOR (HEATER CONTROL 1ST)
CN24-2
CONNECTOR (HEATER CONTROL 2ND)
CN25
CONNECTOR (HUMIDITY OUTPUT)
CN2A
CONNECTOR (0-10V ANALOG INPUT)
CN2C
CONNECTOR (ERV OUTPUT)
CN2L
CONNECTOR (LOSSNAY)
CN32
CONNECTOR (REMOTE SWITCH)
CN41
CONNECTOR (HA TERMINAL-A)
CN51
CONNECTOR (CENTRALLY CONTROL)
CN90
CONNECTOR (WIRELESS)
CN105
CONNECTOR(RADIO FREQUENCY INTERFACE)
CNER
CONNECTOR (ERV INPUT)
CNF
CONNECTOR (HUMIDITY INPUT)
LED1
LED(POWER SUPPLY)
LED2
LED(REMOTE CONTROLLER SUPPLY)
LED3
LED(TRANSMISSION INDOOR-OUTDOOR)
I.B.
5
CN32
4
(RED)
3
CN105
2
1
LED2
(BLACK)
CN2A
SWE
CN41
(RED)
CN25
(BLUE)
2
CNER
1
CN22
(BLACK)
(BLUE)
CN51
CN2C CN24-2
(BLUE)
CNXB2
LED1
CNXA2
(RED)
(YELLOW)
(RED)
1
1
2
1
CN20
CN24-1
CN2L
CNXC2
2
3
2
3
1
4
1
3
4
2
5
2
4
TH1
SYMBOL
NAME
I.B.
INDOOR CONTROLLER BOARD
SW1
SWITCH (FOR MODEL SELECTION)
SW2
SWITCH (FOR CAPACITY CODE)
SW5
SWITCH (FOR MODE SELECTION)
SWE
CONNECTOR (EMERGENCY OPERATION)
P.B.
POWER SUPPLY BOARD
F01
FUSE AC250V 6.3A
ZNR01,02
VARISTOR
DSA
ARRESTOR
X10
AUX. RELAY
TH1
INTAKE AIR TEMP. THERMISTOR
TH2
PIPE TEMP. THERMISTOR/LIQUID
TH5
COND./EVA.TEMP. THERMISTOR
TERMINAL BLOCK
TB4
(INDOOR/OUTDOOR CONNECTING LINE)
TERMINAL BLOCK
TB15
(REMOTE CONTROLLER TRANSMISSION LINE)
RFI
RADIO FREQUENCY INTERFACE FOR RF THERMOSTAT
RFI
INSIDE SECTION OF CONTROL BOX
P.B.
CND
1
3
5
(RED)
DSA
F01
U
ZNR01
ZNR02
U
DC280-340V
X10
RECTIFIER CIRCUIT
(BLUE)
CNXB1
CNXC1 CNXA1
CNMF
76 5 4
1
1 2 3
4
5
1 2
1
2
3
4
MS
3~
FAN MOTOR
SYMBOL
NAME
OPTIONAL PARTS
W.B.
IR WIRELESS REMOTE CONTROLLER BOARD
RU
RECEIVING UNIT
BZ1
BUZZER
LED1
LED(RUN INDICATOR)
SW1
SWITCH(HEATING ON/OFF)
SW2
SWITCH(COOLING ON/OFF)
R.B.
WIRED REMOTE CONTROLLER BOARD
TERMINAL BLOCK
TB6
(REMOTE CONTROLLER TRANSMISSION LINE)
14
TRANSMISSION
WIRES DC 12V
TB15
TB6
1
1
2
2
R.B.
REMOTE CONTROLLER
TB4
S1
OPTIONAL PARTS
S2
TO OUTDOOR UNIT
S3
SWITCH
MODEL
ON
ON
ON
PVA-A30AA4
1
2
3
4
5
1
2
3
4
5
1
2
3
4
ON
ON
ON
PVA-A36AA4
1
2
3
4
5
1
2
3
4
5
1
2
3
4
ON
ON
ON
PVA-A42AA4
1
2
3
4
5
1
2
3
4
5
1
2
3
4
Note1.Since the outdoor side electric wiring may change be sure
to check the outdoor unit electric wiring for servicing.
2.Indoor and outdoor connecting wires are made with
polarities,make wiring matching terminal numbers
(S1,S2,S3).
3.Symbols used in wiring diagram above are as follows.
:CONNECTOR
:TERMINAL
(HEAVY DOTTED LINE):FIELD WIRING
(THIN DOTTED LINE):OPTIONAL PARTS
4.Use copper supply wire.
UTILISER DES FILS D'ALIMENTATION EN CUIVRE.
5
6 8
7
5
6 8
7
5
6 8
7

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Pva-a42aa4Pva-a36aa4

Table of Contents