Stand-alone keypad

Advertisement

This example uses two 917 keypads to operate the same electric locking device. 917 #1 is considered the master unit
and should be located within in the secured area. 917 #2 is the considered a remote egress device and is connected
remote egress device terminal (EG) of the master unit.
When programming 917 #2, set the Relay Time (programming option 40) to 1 second. Use the Set Relay Time
(programming option 40) on 917 #1 to set the unlock time when accessed by either keypad. The latching function
(programming option 41) is only available at the master keypad.
Keypad #1 (Master)
(+)
Power Supply
120VAC input
24VDC Output
This example uses two 917 keypads to operate the same electric locking device. Power for the electric locking device is
wired through both keypads.
All programming functions of each keypad are independent from each other. Set Relay Time (programming option 40)
must be set on each keypad. The latching function (programming option 41) is available at both keypads.
Keypad #1
(+)
Power Supply
120VAC input
24VDC Output
(-)
MOV
Electric Strike
24VDC
(-)
MOV
Electric Strike
24VDC
Example #4
N/O
Egress
Device
Example #5
N/O
Egress
Device
Keypad #2 (Remote)
Keypad #2
N/O
Egress
Device