BOILER OPERATING INSTRUCTIONS
TO SHUT DOWN:
1. Close manual main shut-off valve(s) and pilot
valve(s).
2. Turn off main electric switch.
TO START UP:
1. Make sure that both the main manual and the pilot
valve(s) have been off for at least five minutes.
2. Turn room thermostat and all operating controls to
lowest setting.
3. Remove burner access panel(s).
4. Open manual pilot valve(s).
5. Turn on main electric switch.
6. Reset safety switch on flame safeguard relay.
7. Intermittent electric ignition rectification pilot(s)
Q179C light up automatically when thermostat or
operating control calls for heat.
8. Replace burner access panel(s).
9. Open manual main shut-off valve(s).
10. Adjust room thermostat and operating controls to
desired setting.
Figure 43: Lighting / Operating Instructions (EP-CSD-1)
53