Lochinvar SYNC SBN1000 Recommendation Table
Lochinvar SYNC SBN1000 Recommendation Table

Lochinvar SYNC SBN1000 Recommendation Table

Pumps for sync boilers recommendations
Hide thumbs Also See for SYNC SBN1000:

Advertisement

Temperature Rise
20°F Δ T
Boiler
Flow
Head
Rate
Loss
SBN1000
GPM
Ft/Hd
55.0
31.0
Boiler
Flow
Head
Rate
Loss
SBN1300
GPM
Ft/Hd
65.0
30.0
Boiler
Flow
Head
Rate
Loss
SBN1500
GPM
Ft/Hd
74.0
33.0
This chart provides Pump recommendations for SYNC boilers for the Boiler Loop / Space Heating piping.
Based on specific Temperature Rises, this chart includes calculated Gallon Per Minute flow rate, calculated Foot Head Loss and recommended Pump.
The GPM, Ft/Hd and Pump selection is based on Primary / Secondary Boiler Loop piping of maximum 20 feet of straight pipe, 4 - 90° elbows and 2 - full port ball valves.
See the Installation and Operation manual for more details including pipe diameters and piping diagrams.
Reminder: The SYNC boiler requires TWO pump, one for each heating module.
The Pump recommendations listed above are for the individual heating module.

SYNC PUMP RECOMMENDATION TABLE

Temperature Rise
25°F Δ T
Pump
Flow
Head
Rate
Loss
N/A
GPM
Ft/Hd
44.0
22.0
Pump
Flow
Head
Rate
Loss
N/A
GPM
Ft/Hd
52.0
20.0
Pump
Flow
Head
Rate
Loss
N/A
GPM
Ft/Hd
60.0
23.0
Temperature Rise
30°F Δ T
Pump
Flow
Head
Rate
Loss
PUM30001
GPM
Ft/Hd
38.0
18.0
Pump
Flow
Head
Rate
Loss
PUM30001
GPM
Ft/Hd
45.0
16.0
Pump
Flow
Head
Rate
Loss
PUM30001
GPM
Ft/Hd
51.0
18.0
Temperature Rise
35°F Δ T
Pump
Flow
Head
Rate
Loss
PUM30001
GPM
Ft/Hd
32.0
13.0
Pump
Flow
Head
Rate
Loss
PUM30001
GPM
Ft/Hd
37.0
11.0
Pump
Flow
Head
Rate
Loss
PUM30001
GPM
Ft/Hd
42.0
12.0
Pump
PUM30001
Pump
PUM30001
Pump
PUM30001