(5) Operation data during emergency operation
During emergency operation, no communication is performed with the indoor unit, so the data items needed for operation
are set to the following values:
Operation data
Room temperature (TH1)
Indoor pipe temperature (TH2)
Indoor 2-phase pipe temperature (TH5)
Set temperature
Outdoor pipe temperature (TH3)
Outdoor discharge pipe temperature (TH4)
Outdoor 2-phase pipe temperature (TH6)
Outdoor air temperature (TH7)
Temperature difference code (room temperature - set temperature) (Tj)
Discharge superheat (SHd)
Sub-cool (SC)
1: If the thermistor temperature data is normal (not open/short), that data is loaded into the control as valid data.
If the unit enters emergency operation because TH values have become mismatched, setting the thermistors
to open/short corrects the settings.
2: If one thermistor is set to open/short, the values for each will be different.
[Example] When liquid temperature thermistor (TH3) has an open or short circuit.
Thermistor
TH3
TH6
TH4
TH5
TH2
Discharge superheat (SHd)
Cooling = TH4 - TH6 = Tc - Ta
Heating = TH4 - TH5 = Td - 50
Degree of subcooling (SC)
Cooling = TH6- TH3 = Ta -45
Heating = TH5- TH2 = 50 - 45 = 5
OCH424E
COOL
HEAT
5
45
Tb
Ta
Regard normal figure as effective data.
Td
Tc
Regard normal figure as effective data.
5
50
45
5
Operation mode
COOL
HEAT
27
20.5
5
45
5
50
25
22
45
5
80
80
50
5
35
7
5
5
30deg
30deg
5deg
5deg
53
Remarks
—
—
—
—
( 1)
( 1)
( 1)
( 1)
—
( 2)
( 2)