Remote Controller Diagnosis - Mitsubishi Electric PUHZ-P200YHA Service Manual

Split-type, heat pump air conditioners
Hide thumbs Also See for PUHZ-P200YHA:
Table of Contents

Advertisement

Press the
button twice within 3 seconds. The self-diagnosis
ON/OFF
address or refrigerant address will blink.
Cancel self-diagnosis.
Self-diagnosis can be cancelled by the following 2 methods.
Press the
button twice within 3 seconds.
CHECK
Press the
ON/OFF
button.

11-3-3. Remote Controller Diagnosis

If the air conditioner cannot be operated from the remote controller, diagnose the remote controller as explained below.
First, check that the power-on indicator is lit.
If the correct voltage (DC12 V) is not supplied to the remote controller, the
indicator will not light.
If this occurs, check the remote controller's wiring and the indoor unit.
Switch to the remote controller self-diagnosis mode.
Press the
button for 5 seconds or more. The display content
CHECK
will change as shown below.
Remote controller self-diagnosis result
[When the remote controller is functioning correctly]
Check for other possible causes, as there is no problem with the remote
controller.
[Where the remote controller is not defective, but cannot be operated.]
(Error display 2)
[E3], [6833] or [6832] blinks.
Transmission is not possible.
There might be noise or interference on the transmission path, or the indoor
unit or other remote controllers are defective. Check the transmission path
and other controllers.
To cancel remote controller diagnosis
Press the
button for 5 seconds or more. Remote controller diagnosis will be cancelled, "PLEASE WAIT" and operation lamp will blink. After
CHECK
approximately 30 seconds, the state in effect before the diagnosis will be restored.
OCH424E
When the error history is reset, the display will look like the one shown below.
However, if you fail to reset the error history, the error content will be displayed
again.
Self-diagnosis will be cancelled and the screen will return to the previous state in effect before the
start of self-diagnosis.
Self-diagnosis will be cancelled and the indoor unit will stop.
Press the
[When the remote controller malfunctions]
(Error display 1) "NG" blinks.
The remote controller must be replaced with a new one.
(Error display 3) "ERC" and the number of data errors are displayed.
The number of data errors is the difference between the number of bits sent
from the remote controller and the number actually transmitted through the
transmission path. If such a problem is occurring, the transmitted data is
affected by noise, etc. Check the transmission path.
When the number of data errors is "02":
Transmission data from remote controller
Transmission data on transmission path
24
Power on indicator
button to start self-diagnosis.
FILTER
The remote controller's transmitting-receiv-
ing circuit is defective.