Mitsubishi Electric PUHZ-P200YHA Service Manual page 35

Split-type, heat pump air conditioners
Hide thumbs Also See for PUHZ-P200YHA:
Table of Contents

Advertisement

Error Code
Abnormal point and detection method
Communication error with communica-
tion processor
Defective communication between unit
processor and transmission processor
Note) The address and attribute displayed
A6
at remote controller indicate the con-
(6606)
troller that detected abnormality.
NO ACK signal
1. Transmitting side controller detects
abnormality if a message was transmit-
ted but there is no reply (ACK) that a
message was received. Transmitting
side detects abnormality every 30 sec-
onds, 6 times continuously.
Note) The address and attribute displayed
at remote controller indicate the con-
troller that did not reply (ACK).
A7
(6607)
2. If displayed address or attribute is out-
door unit, indoor unit detects abnormality
when indoor unit transmits signal to out-
door unit and there was no reply (ACK).
3. If displayed address or attribute is indoor
unit, remote controller detects abnormal-
ity when remote controller transmits sig-
nal to indoor unit and there was no reply
(ACK).
OCH424E
Case
1 Data of transmission proces-
sor or unit processor is not
transmitted normally because
of accidental trouble such as
noise or thunder surge.
2 Address forwarding from unit
processor is not transmitted
normally because of defective
transmission processor hard-
ware.
Common factor that has no rela-
tion with abnormality source
1 The unit of former address
does not exist as address
switch has changed while the
unit was energized.
2 Extinction of transmission wire
voltage and signal is caused by
over-range transmission wire.
• Maximum distance.......200m
• Remote controller line...(12m)
3 Extinction of transmission wire
voltage and signal is caused by
type-unmatched transmission
wire.
Type.....
With shield wire-
CVVS, CPEVS
With normal wire (no shield)-
VCTF, VCTFK, CVV
CVS, VVR, VVF, VCT
Diameter.....1.25mm² or more
4 Extinction of transmission wire
voltage and signal is caused
by over-numbered units.
5 Accidental malfunction of
abnormality-detected controller
(noise, thunder surge)
6 Defective of abnormality-gen-
erated controller
1 Contact failure of transmission
wire of outdoor unit or indoor
unit
2 Disconnection of transmission
connector (CN2M) of outdoor
unit
3 Defective transmitting receiving
circuit of outdoor unit or indoor
unit
1 During group operation with
indoor unit of multirefrigerant
system, if remote controller
transmits signal to indoor unit
while outdoor unit power sup-
ply of one refrigerant system
is turned off or within 2 min-
utes of restart, abnormality is
detected.
2 Contact failure of transmission
wire of remote controller or
indoor unit
3 Disconnection of transmission
connector (CN2M) of indoor
unit
4 Defective transmitting receiving
circuit of indoor unit or remote
controller
35
Judgment and action
Turn off the power supply of outdoor unit,
indoor unit and FRESH MASTER or LOSSNAY
at the same time for 2 minutes or more, and
turn the power on again. System returns nor-
mally if abnormality was accidental malfunc-
tion. If the same abnormality generates again,
abnormality-generated controller may be defec-
tive.
Always try the followings when the error
"A7" occurs.
1 Turn off the power supply of outdoor
unit, indoor unit and FRESH MASTER or
LOSSNAY at the same time for 2 minutes
or more, and turn the power on again. If
malfunction was accidental, the unit returns
to normal.
2 Check address switch of abnormality-
generated address.
3 Check disconnection or looseness of
abnormality-generated or abnormality-
detected transmission wire (terminal block
and connector)
4 Check if tolerance range of transmission wire
is not exceeded.
5 Check if type of transmission wire is correct
or not.
If there were some trouble of 1-5 above, repair
the defect, then turn off the power supply of
outdoor unit, indoor unit and FRESH MASTER
or LOSSNAY at the same time for 2 minutes or
more, and turn the power on again.
• If there was no trouble with 1-5 above in
single refrigerant system (one outdoor unit),
controller of displayed address or attribute is
defective.
• If there was no trouble with 1-5 above in
different refrigerant system (2 or more outdoor
units), judge with 6.
6 If address of abnormality source is the
address that should not exist, there is the
unit that memorizes nonexistent address
information. Delete useless address
information with manual setting function of
remote controller.
Only the system FRESH MASTER or
LOSSNAY are connected to, or the system
that is equipped with group setting of
different refrigerant system.
If there was no trouble with 1-6 above, replace
the controller board of displayed address or
attribute.
If the unit does not return to normal, multi-
controller board of outdoor unit may be
defective (repeater circuit).
Replace multi-controller board one by one to
check if the unit returns to normal.
Continued to the next page