Mitsubishi Electric PKH18FK3 Technical & Service Manual page 46

Table of Contents

Advertisement

Check
Diagnosis of malfunction
code
E0
Signal transmitting/receiving
error
(Indoor controller does not
respond to remote controller
signal.)
P1
Abnormality of room temper-
ature thermistor (RT1)
P2
Abnormality of indoor coil
thermistor (RT2)
P3
Signal transmission error
(Remote controller does not
respond to indoor controller
signal.)
P4
Abnormality of drain sensor
P5
Malfunction of drain pump
P6
Freezing protection/
overheating protection
is working.
P7
System error
P8
Abnormality in outdoor unit
Cause
During individual unit control
1) Bad contact of transmission
wire
2) Signal transmitting/receiving cir-
cuit is abnormal.
1) Bad contact of thermistor
2) Damaged thermistor
1) Bad contact of transmission
wire
2) Signal transmitting/receiving cir-
cuit is abnormal.
3) Wrong operation due to noise
wave emitted by other appli-
ances
1) Bad contact of transmission
wire
2) Damaged thermistor
1) Malfunction of drain pump
2) Damaged drain sensor
1) Short cycle of air cycle
2) Dirty air filter
3) Damaged fan
4) Abnormal refrigerant
1) Wrong address-setting
2) Signal transmitting/receiving cir-
cuit of remote controller is
abnormal.
3) Wrong SW6-setting
1) Wrong wiring of indoor/outdoor
connecting wire
2) Reversed phase
3) Protection device is working
4) Damaged outdoor coil thermis-
tor
46
Check points
1) Check the transmission wire.
2) Check with another remote controller. If "E0" is
still indicated, replace the indoor controller
board.
If other check code appears. replace the origi-
nal remote controller.
1) Check the thermistor.
2) Measure the resistance of the thermistor.
Normal resistance should be as follows.
32°F····15kΩ
86°F·····4.3kΩ
50°F······9.6kΩ 104°F ···3.0kΩ
68°F······6.3kΩ
If the resistance is normal, replace the indoor
controller board.
1) Check the transmission wire.
2) Check with another remote controller.
If "P3" is still indicated, replace the indoor
board.
If other check code appears, replace the origi-
nal remote controller.
1 and 2 of CN40 and
3) Short-circuit between
attach CN40 to the following units.
Second unit in twin control
Second and third units in triple control
Sub units in group control
1) Check the connector.
2) Measure the resistance of the thermistor 1 - 3.
32°F ···6kΩ
59°F ···3.2kΩ 86°F ···1.8kΩ
41°F ···4.8kΩ 68°F ···2.6kΩ 95°F ···1.5kΩ
50°F ···3.9kΩ 77°F ···2.2kΩ 104°F 1.3kΩ
If the resistance is normal, replace the indoor
controller board.
1) Check the drain pump.
2) Check the drain sensor.
(Check the drop of water is on.)
If the resistance is normal, replace the indoor
controller board.
1) Clear obstructions from the air cycle.
2) Clean the air filter
3) Check the fan.
4) Check the refrigerant temperature.
1) Check the address-setting.
2) Check with another remote controller. If check
code other than "P7" appears, replace the origi-
nal remote controller.
3) Check SW6 setting.
1) Check the indoor/outdoor connecting wire.
2) Change the connection of electric wiring.
3) Check the protection device.
4) Measure the resistance of the outdoor coil ther-
mistor. If the resistance is normal, replace the
outdoor controller board.