Real Fires Minimal Range installation instructions
INSTALLATION INTO TIMBER FRAMING
AND NEW MASONRY BLOCK CONSTRUCTION
New Masonry Block The following instructions are for installation into timber frame.
The method of installation is the same for New Masonry Block.
See Masonry Block Drawing
Ventilation
Ventilation to the room that houses the fire must meet the requirements of NZ5261
Framing Details
Prior to installation, timber framing needs to be provided to suit the selected Real
Fire. See installation drawing
Hearth
A non combustible Hearth must be provided in front of the Real Fire unless the
flooring in front of the fire is non combustible. The minimum size is 300mm out from
the fire and 150mm each side wider than the fire.
Height of fire from floor
It is important to confirm the height the fire is to be installed from the floor level. This
is usually the hearth height. For example if the hearth is 100mm high then the fire
needs to be installed 100mm high. ( note- some elevated installations specify the fire
higher than the hearth). Once the height is confirmed a platform needs to be built to
support the firebox. The platform can be of timber construction. It needs to be sturdy
and level.
Gas Supply
A suitable gas supply needs to be provided at the right hand rear corner of the timber
frame cavity. The pipe sizing should be calculated to supply gas to suit the megajoule
rating of the fire. See rating chart. The gas supply should be reduced down to 10mm
copper pipe at the fireplace location and left with a coil of approx 1 metre to feed into
the firebox.
Gas Rate Chart
Minimal Model
Model 800
800
1000
1200
LPG
40 MJ/h
51 MJ/h
64 MJ/h
Natural Gas
40 MJ/h
51 MJ/h
59 MJ/h
Need help?
Do you have a question about the 800 and is the answer not in the manual?
Questions and answers