<When the installation plate is directly mounted on
the wall>
1. Securely fit the installation plate onto the wall by
screwing it in the upper and lower parts to hook up
the indoor unit.
2. To mount the installation plate on a concrete wall
with anchor bolts, utilize the anchor bolt holes as
illustrated in the above figure.
3. Install the installation plate horizontally in the wall.
CAUTION
When installing the installation plate with a
mounting screw, do not use the anchor bolt hole.
Otherwise the unit may fall down and result in
personal injury and property damage.
Installation plate
<Keep horizontal direction>
5 mm dia. hole
Clip anchor
(local parts)
Fig. 8-4-4
CAUTION
Failure to firmly install the unit may result in
personal injury and property damage if the unit falls.
• In case of block, brick, concrete or similar type
walls, make 5 mm dia. holes in the wall.
• Insert clip anchors for appropriate 7 mounting
screws.
NOTE
• Secure four corners and lower parts of the
installation plate with 4 to 6 mounting screws to
install it.
Anchor
bolt
Projection
15 mm or less
7
7
7
7 Mounting
7
screw
∅4 x 25s s s s s
− 44 −
FILE NO. SVM-05020
8-4-3. Electrical work
1. The supply voltage must be the same as the rated
voltage of the air conditioner.
2. Prepare the power source for exclusive use with the
air conditioner.
CAUTION
• This appliance can be connected to the mains in
either of the following two ways.
(1) Connection to fixed wiring:
A switch or circuit breaker which disconnects
all poles and has a contact separation of at
least 3 mm must be incorporate in the fixed
wiring. An approved circuit breaker or
switches must used.
(2) Connection with power supply plug:
Attach power supply plug with power cord
and plug it into wall outlet. An approved
power supply cord and plug must be used.
NOTE
• Ensure all wiring is used within its electrical rating.
RAS-13UKHP-ES4
Model
RAS-13UKP-ES4
Power source
50 Hz, 220 − 240 V Single phase
Maximum
12A
running current
Plug socket &
fuse rating
Power cord
1.3 mm
RAS-10UKHP-ES4
RAS-10UKP-ES4
RAS-07UKP-ES4
7.5A
16A
or more
1 mm
or more
2
2