1.0
SPECIAL NOTICES
1.1
The
following
important information in the installation and
maintenance sections. Each serves a special
purpose and is displayed in the format shown:
This symbol indicates a potentially hazardous
situation, which, if not avoided, can result in
personal injury or damage to the equipment.
CAUTION
This symbol indicates a potentially hazardous
situation, which, if not avoided, may be a
shock hazard.
CAUTION
This symbol indicates an imminently hazardous
situation, which, if not avoided, could result in
death or serious injury.
WARNING
2.0
PRE-INSTALLATION
2.1
Initially, inspect the heater for possible
damage due to shipping and handling. Claims
for shipping damages shall be placed with the
carrier.
2.2
Check the heater nameplate to ensure that
the heater area classification and temperature
code are suitable for the hazardous area
classification.
locations with potential for explosion, refer
to the Canadian Electrical Code or National
Electrical Code.
2.3
Check to ensure that the heater voltage is the
same as the supply voltage.
2.4
The heater must be installed by qualified
personnel in strict compliance with national
and local electrical codes.
DO NOT CONNECT THE HEATER TO AN
ELECTRICAL SUPPLY VOLTAGE OTHER
THAN THAT SHOWN ON THE PRODUCT
WARNING
NAMEPLATE.
E-mail: info@ccithermal.com
Printed In Canada
special
notices
highlight
For
details
of
hazardous
TYPE XB EXPLOSION-PROOF
CONVECTION PANEL HEATER
INSTALLATION, OPERATION &

MAINTENANCE INSTRUCTIONS

3.0
INSTALLATION - GENERAL REQUIREMENTS
3.1
Norseman
or floor mounting with the terminal housing at
the bottom. Ensure that is the wall sufficiently
strong to support the heater which, depending
on the model, could weigh up to 100 lbs (45
kg). Otherwise use the brackets supplied to
stand the heater on the floor.
3.2
Do not recess the Norseman
into the wall. Use of the brackets supplied will
ensure that the minimum spacing from the
wall of 3.75" (95 mm) is maintained.
3.3
If more than one heater is being installed,
maintain at least 3" (76 mm) between adjacent
heater extrusions. NEVER INSTALL ONE
HEATER ABOVE THE OTHER.
3.4
The Norseman
convection and "black heat" radiation to transfer
heat to the surroundings. Try to maintain a 12"
(300 mm) clearance and NEVER LESS THAN
6" (150 mm) clearance in front of and at the
sides of the heater.
3.5
Use guard rails in front of the heater if there
is a possibility that moving equipment could
come in contact with the heater.
®
C
US
ISO 9001
XB heaters are approved for wall
TM
TM
XB heater relies on natural
TM
www.ccithermal.com
Date of Issue: October 2014
10457.Rev.2.03
XB heater

Advertisement

Table of Contents
loading

Summary of Contents for Norseman XB1

  • Page 1: Maintenance Instructions

    CAUTION Do not recess the Norseman XB heater This symbol indicates a potentially hazardous into the wall. Use of the brackets supplied will...
  • Page 2 INSTALLATION - REFLECTOR BAFFLES REFLECTOR BAFFLES (T2D units only). Refer to Figure 1 when installing reflector baffles. FIGURE 1 - REFLECTOR BAFFLES INSTALLATION TABLE 1 - REFLECTOR BAFFLE PAIRS PER HEAT SINK Heat Sink Extrusion Size Length # of Pairs 11.8 18.5 25.2...
  • Page 3: Wall Mounting

    WALL MOUNTING FLOOR MOUNTING Install heater with the supplied hardware in Step 1: Position heater face down on the floor accordance with the Figures and instructions with terminal box towards the wall (Figure 6). below. Step 1: Secure wall and stabilizing brackets to mounting surface (Figure 3).
  • Page 4 Slide well over bulb and screw into place. Make sure that a minimum 5 threads engagement is achieved. FIELD INSTALLED KIT - Most Norseman XB units are suitable for field installation of a thermostat kit with the operator shaft hole on the...
  • Page 5: Maintenance

    10.0 MAINTENANCE WHENEVER HAZARDOUS MATERIALS ARE PRESENT, ENSURE THAT THE TERMINAL 10.1 Periodically inspect the heater installation to HOUSING COVERS, PLUGS, ETC., ARE ensure that all connections, fittings, plugs, SECURED (BUT NOT OVER-TIGHTENED) screws, covers, etc. are tight and free of WARNING BEFORE ENERGIZING THE HEATER.
  • Page 6 NOTES...
  • Page 7 NOTES...
  • Page 8 5918 Roper Road, Edmonton, Alberta, Canada T6B 3E1 Phone: (780) 466-3178 Fax: (780) 468-5904 PLEASE ADHERE TO INSTRUCTIONS PUBLISHED IN THIS MANUAL. Failure to do so may be dangerous and may void certain provisions of your warranty. For further assistance, please call: 24 Hr.