Install the DeviceNet bulkhead connector by removing
the plastic plug covering the circular hole (ITEM 4) in
the front lower panel assembly. Install the 5-pin con-
nector and mounting plate over the mounting studs as
shown in (Figure A.1). Fasten with two of the supplied
locknuts.
If a Wire Drive Interface Module is not installed
(Figure A.1), locate the 6-pin to 4-pin interconnect.
Insert the interconnect between J73 on the DeviceNet
module and J16 in the machine harness. Discard the
4-pin to 4-pin interconnect and proceed to the next
section.
If a Wire Drive Interface Module is installed (Figure
A.2), locate the 4-pin to 4-pin interconnect. Insert the
interconnect between J73 on the DeviceNet module
and J81 on the Wire Drive Interface Module. Discard
the 6-pin to 4-pin interconnect.
ONLY FOR MACHINES WITH A DEVICENET MODULE
AND A WIRE DRIVE INTERFACE MODULE
FIGURE A.2
DeviceNet Baud rate: The default Baud rate is 125K.
If another Baud rate is desired, see table 2 in this sec-
tion and set switches 1 and 2 of bank S2. Every
device on a DeviceNet network must have the same
Baud Rate.
DeviceNet Module DIP Switches:
Bank S1
switch 1 = Object Instance LSB (Default = OFF)
(See Table 1)
switch 2 = Object Instance MSB (Default = OFF)
(See Table 1)
Object Instance (Table 1)
Switch 2
Switch 1
Off
Off
Off
On
On
Off
On
On
INSTALLATION
4-pin to 4-pin interconnect
Wire Drive Module
Instance
0
1
2
3
DEVICENET MODULE
switch 3 = Equipment Group 1 Select (Default = Off)
switch 4 = Equipment Group 2 Select (Default = Off)
switch 5 = Reserved for future use
switch 6 = Reserved for future use
switch 7 = Reserved for future use
switch 8 = Reserved for future use
Bank S2
switch 1 = DeviceNet Baud Rate (Default = OFF)
(See Table 2)
switch 2 = DeviceNet Baud Rate (Default = OFF)
(See Table 2)
DeviceNet Baud Rate (Table 2)
Switch 1
Switch 2
Off
Off
On
Off
On
On
On
On
switch 3 = DeviceNet Mac ID (Default = Off)
(See Table 3)
switch 4 = DeviceNet Mac ID (Default = On)
(See Table 3)
switch 5 = DeviceNet Mac ID (Default = On)
(See Table 3)
switch 6 = DeviceNet Mac ID (Default = On)
(See Table 3)
switch 7 = DeviceNet Mac ID (Default = On)
(See Table 3)
switch 8 = DeviceNet Mac ID (Default = On)
(See Table 3)
DeviceNet MAC ID:
The default Mac ID is 62. Every device on the
DeviceNet network should have a unique ID. If anoth-
er MAC ID is desired, refer to Table 3.
• Complete Board Installation
Close door assembly insuring not to cut or
pinch any wires.
Reinstall the screws in door assembly.
Re-apply power and verify the appropriate
status lights on the Power Wave are green.
Discard any remaining hardware.