Dale Power Solutions Ltd User Manual E200 Series UPS E201(E) E202(E) E203(E) Dale Power Solutions Ltd Salter Road, Eastfield Industrial Estate, Scarborough, North Yorkshire, YO11 3DU, UK info@dalepowersolutions.com | www.dalepowersolutions.com | +44 (0) 1723 583511 S5264FU01 Rev 3...
Page 2
Dale Power Solutions Ltd reserves the right to make changes in specification without notice or liability. All information is subject to Dale Power Solutions Ltd own data and is considered accurate at time of publishing.
Safety instructions in this manual are supplementary to local safety instructions. Dale Power Solutions does not accept any liability caused as a result of failure to follow safety instructions. Please note the following: Do not operate the UPS in an environment or application outside of that detailed in the user manual.
Dale Power Solutions Ltd User Manual Product description Applications This UPS series provides reliable AC backup power to various types of equipment, for example computer centres, network management centres, auto control systems, and telecommunication systems. Product range The following table lists the models available in the E200 series. Models with an E suffix are designed for operation with an external battery.
Dale Power Solutions Ltd User Manual System block diagram A functional block diagram representing the UPS is shown in Figure 1. Power is delivered to the output via one of these three paths; a) via the bypass, b) directly through the AC/DC converter and inverter, or c) from the battery via the DC/DC converter and inverter.
Dale Power Solutions Ltd User Manual Installation Siting considerations Before unpacking and installing the unit, consider the following: ■ DO NOT expose the UPS to high temperatures, water ingress, flammable or corrosive gas, dust, direct sunlight or explosives. ■ Locate the UPS indoors on a level surface as close as possible to the equipment it will be powering to minimise cable voltage drops.
Dale Power Solutions Ltd User Manual Rear panel layout Figure 2 and Figure 3 show the rear panel connections for the two sizes of UPS. Surge protected network connection Figure 2 Rear panel layout (1 kVA unit) Surge protected network connection Figure 3 Rear panel layout (2/3 kVA units) …………………………………………………………………………………………………………...
Plug the battery cable into the rear of the UPS (see Figure 2 or Figure 3). 2. Using the supplied cables, connect the UPS output(s) to your load(s). The E201(E) has three IEC output sockets, and the E202(E) and E203(E) have four IEC outputs plus a high current IEC output.
Dale Power Solutions Ltd User Manual Operation Working modes The UPS has four distinct modes of operation: ■ On-line mode ■ Bypass mode ■ Battery mode ■ ECO mode Each operating mode is described below. On-Line mode This is the default mode of operation in which the load is supplied via the AC/DC converter and inverter when the a.c.
Dale Power Solutions Ltd User Manual Front panel controls and indicators The front panel controls and indicators are shown in Figure 4. Using the buttons, LEDs and the menu structure displayed on the LCD panel you can: ■ Check the status of the UPS ■...
Dale Power Solutions Ltd User Manual LCD display The LCD display comprises a battery capacity graphics section, a fan status section, a charge status section, and a numerical value section as shown below. Loading & battery capacity: number of panes lit indicates the value; top=load,...
Dale Power Solutions Ltd User Manual 3. On the front panel, press and hold (see Figure 4 on page 12) until a beep is heard (after approximately half a second). The LEDs flash initially and then the green inverter LED ( ) should be on.
Dale Power Solutions Ltd User Manual ECO mode To turn on ECO mode: 1. On the front panel, press for more than 2 s. The following is displayed. characters flash 2. Press for more than 0.5 s but less than 2 s. The following is displayed.
Dale Power Solutions Ltd User Manual 3. Press for more than 0.5 s but less than 2 s. The following is displayed. characters flash 4. Press for more than 0.5 s but less than 2 s. OFF stops flashing. 5. Press to display ON, which flashes.
Dale Power Solutions Ltd User Manual 4. Press for more than 0.5 s but less than 2 s. OFF stops flashing. 5. Press to display the output voltage you require. The voltages provided are 208 V, 220 V, 230 V (the default value) and 240 V.
Dale Power Solutions Ltd User Manual Fault mode In fault mode the UPS cuts off the output or switches to bypass mode, and sounds the buzzer. The warning LED is lit and the display shows a fault code. A list of fault codes is shown on page 26.
Dale Power Solutions Ltd User Manual Maintenance E200 series units use sealed lead acid, maintenance free batteries and require minimum maintenance in general. To keep the batteries fully charged and in good condition, ensure the UPS is plugged into the mains at all times.
Dale Power Solutions Ltd User Manual Function check Perform a self test every 6 months as described on page 14. Troubleshooting Before contacting your distributor, try to solve your problem using the information in the following table. If you need to contact your distributor make sure you have the model number and serial number of your UPS.
Dale Power Solutions Ltd User Manual Appendix 1 Signals options RS232 serial port Units are fitted with a standard RS232 serial port, which can be used to: ■ Monitor the UPS power status ■ Monitor the UPS alarm information ■...
Dale Power Solutions Ltd User Manual Relay card (advanced monitoring and control) If your unit has been specified and fitted with the optional relay card (located in the Intelligent Slot on the rear panel) you have access to more advanced monitoring and control functionality via a set of dry contacts and a single opto-coupled input.
Page 23
Dale Power Solutions Ltd User Manual Opto-coupler input specifications (used for remote shutdown): Parameter Value Reverse voltage (V 6 V d.c. Forward input voltage 30 V d.c. max., 5 to 12 V d.c. typical Forward current 80 mA max., 16 mA typical 1 A (100 μs pulse, 100 pps)
E203, E203E: 72 V Internal battery type 12 V, 9 AH VRLA maintenance free Backup time E201, E202, E203: > 4 mins. Suffix E backup time is determined by the size of the external battery Charge current E201, E202, E203: 1 A...
Dale Power Solutions Ltd User Manual Output ≥84% Efficiency in battery mode ≥94% Efficiency in ECO mode Safety and EMC Safety IEC62040-1 GB4943 Isolation resistance >2 MΩ (500 V d.c.) Isolation voltage 2,820 V d.c., <3.5mA 1 min Conduction: IEC 62040-2...
Dale Power Solutions Ltd User Manual Appendix 3 Optional equipment The following items are available as options for the UPS: ■ Extension battery box ■ Dry contact relay card ■ SNMP card ■ Battery MCB box ■ Bypass panel Appendix 4 Fault codes...
Dale Power Solutions Ltd User Manual Appendix 5 LED indicator status Working status Beeps Comments On-line mode Normal voltage None High/low mains, in battery mode Every 4 s ECO mode Normal voltage None High/low mains, in battery mode Every 4 s...