Viessmann VITODENS 200-W Technical Manual page 74

Gas condensing boiler
Table of Contents

Advertisement

Control units
(cont.)
– Forwarding messages via email to terminal devices with email cli-
ent function
– Forwarding messages via SMS to mobile phone/smartphone or
fax (via chargeable internet service Vitodata 100 fault manage-
ment)
– Monitoring of additional devices via the inputs and outputs of the
Vitocom and EM301 extension modules
■ Remote control:
Selecting operating programs, set values, time programs and heat-
ing curves
Note
■ Telecommunication costs for data transfer are not included in the
device price.
■ For more information, see www.vitodata.info.
Functions when operating with Vitodata 300:
For all heating circuits in a heating system:
■ Remote monitoring:
– Forwarding of messages via SMS to mobile phone/smartphone,
via email to end devices with email client functionality or via fax to
fax machines
– Monitoring of additional devices via the inputs and outputs of the
Vitocom 300
■ Remote control:
– Selecting operating programs, set values, time programs and
heating curves
– Recording trends via datalogger
– Recording of energy consumption through integration of M BUS
heat meters
■ Remote setup:
– Configuring Vitocom 300 parameters
– Remote setup of Vitotronic control parameters via coding
addresses
Note
■ Alongside the data transfer telecommunication costs, usage
5
charges have to be taken into account for Vitodata 300.
■ For more information, see www.vitodata.info.
Configuration
■ In the case of dynamic IP addressing (DHCP), the IP configuration
of the Vitocom 300 occurs automatically.
No adjustments have to be made on the DSL router.
■ Observe the network settings of the DSL router.
■ The outputs and inputs of the Vitocom 300 and EM301 extension
module are configured using the Vitodata 300 user interface.
■ The Vitocom 300 is connected to the Vitotronic control unit via LON.
The Vitocom 300 does not need to be configured for the LON.
Fault messages
Fault messages are reported to the Vitodata server. These messages
are transmitted via the following communication services from the
Vitodata server to the configured recipients:
■ Fax
■ SMS to mobile phones
■ Email to PC/laptop
On-site requirements:
■ DSL router with free LAN socket and dynamic IP addressing (DHCP)
■ Internet connection with flat rate data (without time or volume
restrictions)
■ LON communication module must be installed in the Vitotronic appli-
ance
Note
For more information, see www.vitocom.info.
VIESMANN
74
Standard delivery:
■ Vitocom 300, type LAN3 with LAN socket
– Mounting rail installation TS35 to EN 50022,
35 x 15 and 35 x 7.5
– 2 digital inputs
– 1 digital output
– 1 relay output
– 1 M BUS interface
– 1 EM interface
– 2 LON connections
■ LAN cable, RJ45, 2 m long
■ LON communication module
■ LON cable, RJ45 – RJ45, 7 m long, for data exchange between the
Vitotronic control unit and the Vitocom 300
■ Power supply unit for top-hat rail, mounting rail installation TS35 to
EN 50022, 35 x 15 and 35 x 7.5
■ Vitodata 100 fault management for a duration of 3 years
Note
For standard delivery of packs with Vitocom, see pricelist.
Accessories:
Accessories
Wall mounting enclosure for installation of the
Vitocom 300 and accessories if no control panel or
electrical distribution panel is available.
2 rows
3 rows
EM301 extension module
– Mounting rail installation TS35 to EN 50022,
35 x 15 and 35 x 7.5.
– 8 analogue inputs:
– 0 − 10 V–
– 4 − 20 mA
– Viessmann temperature sensors NTC 10 kΩ,
NTC 20 kΩ, Ni500 or Pt500
– Pulse counter
– 8 digital inputs:
– For hooking up signals via floating contacts
– 2-pole
– Breaking capacity of the external contact 24 V–,
7 mA
– With LED indicator
– N/C or N/O contact
– N/C or N/O alarm contact
– Pulse counter
– 2 digital outputs:
– Floating relay contacts
– 3-pole changeover contact
– Max. 2 A, 230 V~
– With LED indicator
Max. 3 x EM301 extension modules per Vitocom 300
Uninterrupted power supply unit (UPS)
Mounting rail installation TS35 to EN 50022,
35 x 15 and 35 x 7.5
Additional rechargeable battery pack for UPS
– Mounting rail installation TS35 to EN 50022,
35 x 15 and 35 x 7.5
– Recommended with 1 Vitocom 300, 1 extension
module and all inputs allocated
– Required from 1 Vitocom 300 and 2 extension mod-
ules
Part no.
7143 434
7143 435
Z012 117
7143 432
7143 436
VITODENS 200-W

Hide quick links:

Advertisement

Table of Contents
loading