Download Print this page

GE Telaire Ventostat 8000 Series User Instructions page 4

Co2 sensor

Advertisement

Power Consumption
Typical 0.7 W at nominal voltage of 24V AC RMS
Temperature Dependence
0.2% FS per °C (±0.11% per °F)
Stability
T8100/T8300 - Single Channel
<2% of FS over life of sensor (15 years)
T8200 - Dual Channel
<5% of FS or <10% reading annual over life of sensor
(10 years)
Pressure Dependence
0.135% of reading per mm Hg
Certifications
CE and RoHS compliant
Signal Update
Every 5 seconds
CO
Warm-up Time
2
< 2 minutes (operational)
10 minutes (maximum accuracy)
Operating Conditions
32°F to 122°F (0°C to 50°C)
0 to 95% RH, non-condensing
Storage Conditions
-40°F to 158°F (-40°C to 70°C)
Flammability Classification
UL94 5VA
Thermistor Type
NTC 10 K thermistor
Thermistor Accuracy
±1°C (15° to 35°C)
RH Sensing Element
Capacitive polymer sensor
Page 4
RH Range
0% to 99% RH (non-condensing)
RH Accuracy (25°C)
±2.5% RH (20 to 80% RH)
±3.5% RH (<20% and >80% RH)
Active Temperature Accuracy
±0.8°C @ 22°C
Active Temperature Range
0 to 50°C
ABC Logic™ Self Calibration System
ABC Logic™ (Automatic Background Calibration) self calibration
allows the sensor to continually recalibrate itself when the indoor
concentrations drop to outside levels while the building is unoccupied.
Generally a building must be regularly unoccupied for 4 hours or more
for this self-calibration system to operate properly. Under these
conditions, ABC Logic™ should maintain sensor calibration over the
lifetime of the sensor. The ABC Logic™ should be turned OFF where a
building is continuously occupied 24 hours per day, or where there could
be significant sources of non-occupant related CO
breweries and other industrial and food processing applications.
Output
Analog
0 to 5 V, (100
output impedance)
0 to 10 V (100
output impedance) and
4 to 20mA (R
maximum 500 ) available simultaneously for CO
L
output
Digital to analog error ±1%
Warranty/Other
Warranty
18 months parts and labor
This product is covered by one or more of the following patents:
5,650,624 / 5,721,430 / 5,444,249 / 5,747,808 / 5,834,777 / 5,163,332 /
5,340,986 / 5,502,308 / 6,344,798 / 6,023,069 / 5,370,114 / 5,601,079 /
5,691,704 / 5,767,776 / 5,966,077 / 6,107,925 / 5,798,700 / 5,945,924 /
5,592,147 / 6,255,653 / 6,250,133 / 6,285,290
Warranty Repairs
GE Sensing will repair Telaire product that fails to meet the terms
provided for in the Return and Warranty Policy Statement (See, http://
www.ge-mcs.com/en/services-and-support.html).Warranty period shall
start from date of manufacture and be based on product category and
type of equipment as specified in Table 1: Product Warranty Periods. For
all warranty repairs, GE Sensing will bear all product repair parts, labor,
and standard ground shipping charges.
such as greenhouses,
2
Telaire Ventostat™ 8000 Series
2

Advertisement

loading