Power Requirements: Single Secondary Input (Primary Offline) - HP StorageWorks XP128 Installation Manual

Hide thumbs Also See for StorageWorks XP128:
Table of Contents

Advertisement

Power requirements: single secondary input (primary offline)

Reference supplier information
Preparing for installation
The values in the table below are based on a worst-case voltage (rated
voltage –10%) and a maximum configuration for disk array control and
disk frames. A phase imbalance of 15% is also included in the calculation.
Input (Vac)
Power Required
208
25.0 A (9.0kVA)
400
16.3 A (11.3k VA)
American Power Conversion
32 Fairgrounds Road
West Kingston, RI 0289
Phone Numbers:
Technical Support & Product Info.
1-800-800-4272
Corporate
1-800-788-2208
1-401-789-5735
To find out more about the recommended American Power Conversion
UPS, travel to the APC web site:
www.apcc.com
You can also contact your HP service representatives for specific
configuration needs for your area.
53

Advertisement

Table of Contents
loading

Table of Contents