FORCED AIR COOLING (FAC) PERFORMANCE DATA (WITH 30PPI FILTER)

# FANS
MODEL #
FAC-190
1
FAC-360
2

ENVIRONMENTAL COOLING MODULE (ECM) PERFORMANCE DATA

MODEL
RATED
SUPPORT
NUMBER
CAPACITY
LOAD
BTUH/Watt
BTUH/Watt
ECM-42
4200/1230
2730/800
ECM-62
6200/1815
4095/1200
ECM-80
8000/2345
5800/1700
ECM Notes:
1. 60Hz: R-22 refrigerant / 50Hz: R-134A refrigerant
2. Two-Speed Operation - Switch low-high speed on ambient temperature external to LGH enclosure
3. Automatic Load Matching: Hot gas by-pass factor set for minimum capacity; by-pass will adjust to
match supported loads
4. Condensate Re-evaporation & Removal: Drain connection only required if enclosure seal is violated.

TABLES

AIRFLOW (w/Filter)
HIGH
LOW
SPEED
SPEED
190 CMF
90 CMF
112 CMH
53 CMH
360 CMF
175 CMF
212 CMH
103 CMH
RATED/MAX
HEIGHT
AMBIENT
60Hz
50Hz
U
In/mm
105F
100F
6
10.5/
41C
38C
265
105F
100F
7
12.3/
41C
38C
310
105F
100F
9
15.8/
41C
38C
400
Standard Offerings - All Systems
SOUND LEVEL
HIGH
LOW
SPEED
SPEED
61 dBa
47 dBa
59 dBa
49 dBa
DIMENSIONS
DEPTH
TOTAL
WIDTH
HEAT REJ.
In/mm
Rack
In/mm
BTUH/Watt
17.5/
19
27/
7625/
445
685
2235
22/
24
27/
11310/
560
685
3315
22/
24
29/
14605/
560
735
4280
11
INPUT POWER (1PH)
FLA / WSA / OPD
120V/60Hz
220V/50Hz
0.5/15/15
0.5/15/15
1.0/15/15
1.0/15/15
INPUT POWER (1PH)
WEIGHT
120V/60Hz
220V/50Hz
(lbs/Kg)
8/15/15
7/15/15
95/43
12/20/20
9/15/15
115/52
16/20/20
16/20/20
167/76