VERTICAL VENTING – NEGATIVE PRESSURE
VENT SIzING
Size the vent pipe according to the venting
using single-wall or double-wall (Type B) gas
the size of the vent pipe adapter on the heater
(see Table 6). The maximum vent height can-
not exceed 50 ft. The total lateral (horizontal)
maximum. Single-wall vent may be used in
Double-wall (Type B) vent must be used in non-
conditioned spaces.
VENT TERMINATION
horizontally from a vertical wall or similar obstruction shall terminate not less than 2 ft above any portion
minimum value of H using Figure 5 and Table 7.
Figure 5
Minimum Height from Roof for Vent Cap
Lowest discharge opening
Listed
cap
Listed gas
vent
H (minimum)-
Minimum height from roof
to lowest discharge opening
-
x
12
Roof pitch is x/12
USE ONLY HAYWARD GENUINE REPLACEMENT PARTS
Table 6
Vent Pipe Diameters for
Negative-Pressure Indoor Vent Kits
Indoor Vent Kit
Part Number
Heater Model
UHXNEGVT11501
UHXNEGVT12001
UHXNEGVT12501
UHXNEGVT13001
UHXNEGVT13501
UHXNEGVT14001
Height Requirements for Vent Caps
(see Figure 5)
Roof Slope
Flat to 6/12
Over 6/12 to 7/12
Over 7/12 to 8/12
Over 8/12 to 9/12
Over 9/12 to 10/12
Over 10/12 to 11/12
Over 11/12 to 12/12
Over 12/12 to 14/12
Over 14/12 to 16/12
Over 16/12 to 18/12
Over 18/12 to 20/12
Over 20/12 to 21/12
Pomona, CA Clemmons, NC Nashville, TN
Tel: 908-351-5400
Vent Pipe
Diameter
H150FD
6 inch
H200FD
6 inch
H250FD
6 inch
H300FD
8 inch
H350FD
8 inch
H400FD
8 inch
Table 7
Min. Height H from Roof to
Lowest
Discharge Opening
1.0 ft
1.25 ft
1.5 ft
2.0 ft
2.5 ft
3.25 ft
4.0 ft
5.0 ft
6.0 ft
7.0 ft
7.5 ft
8.0 ft
www.haywardpool.com