Output character pacing?
If set to YES, this parameter reduces CMnet transmission speed by 50%.
This may be necessary when operating at 38.4k baud with older modules on the same CMnet.
Delay before sending all replies (20 msec minimum) = 20 msec: The time in milliseconds to wait
before replying to CMnet commands. This is necessary to allow the sender time to shut off its
transmitter and prepare to receive the reply. If the reply comes too quickly, it may be missed.
Interpacket delay....... (20 msec minimum) = 20 msec: The delay time in milliseconds between
successive CMnet messages sent by this module. This allows all receiving modules time to take action
on each message.
Alternate interpacket delay... (40 msec minimum) = 40 msec: This parameter is the same as the
Normal interpacket delay parameter, except this delay is used between color update messages which
require more time for the receiving module to process.
CMnet Tuning Parameters
Time to wait before attempting intrusive grab: This is the time allowed after a grab request on a
console port for a non-intrusive grab to be successful before resorting to an intrusive grab. A non-
intrusive grab is when the SiteGate-232 takes control of the CMnet without sending a stream of "!
!
!
!
!..." characters. This can only be successful if the modules on the CMnet employ the "grabless"
token passing scheme. A non-intrusive grab is preferred over an intrusive grab because it is quicker
and non-disruptive.
Maximum number of intrusive grab attempts per request: If the non-intrusive grab is unsuccessful, the
SiteGate-232 will attempt this many intrusive grabs before giving up entirely and returning a negative
acknowledgment on the console port that requested the grab.
Grab Silence Time: The CMnet must be silent for at least this long after an intrusive grab attempt to
consider the grab successful.
Time to hold the token when the token wraps around: When the CMnet token is passed from the
module with the highest CM address to the SiteGate-232 (CM address #1), the SiteGate-232 will hold
the token for this amount of time before passing it to module #2. This is useful for reducing the rate of
time broadcasts on CMnets with low module counts, because the SiteGate-232 broadcasts the time
every time the CMnet token is passed to it.
Time to wait for each module to acknowledge the token: When the SiteGate-232 passes the CMnet
token to a module, it will wait this long for the module to acknowledge that the token was received
before skipping it and passing the token to the next module.
Maximum online time per successful grab: The amount of time any console port is allowed to be online
on the CMnet after each successful grab. If the online time expires, the console port will be
disconnected from the CMnet and the SiteGate-232 will restart the CMnet token.
Maximum monitor time per monitor request: The amount of time any console port is allowed to monitor
the CMnet after each monitor request. If the monitor time expires, the console will be disconnected
from the CMnet and an additional monitor request must be issued to continue monitoring.
Console Port Parameters
Modem installed on this console port = No: This enables the use of a modem on the console port.