Lgm Module Driver Parameters - Liebert 232 User Manual

Liebert user's manual sitegate 232
Table of Contents

Advertisement

If not connected, and with no alarms pending delivery, reset modem
every
5:00 (mm:ss).
If connected, but no activity has been detected for 20:00 (mm:ss),
hang up and reset modem.
After dialing, wait
After unsuccessful alarm delivery, wait
trying again.
Escape (+++) guard time 1000 msec.
Post hangup delay
Reset time (DTR low)
Post DTR high delay
Post reset string delay 1000 msec.
Enable daylight saving time changeover from this module NO .
Do not enable this if you have an XFG, XFR, XFT, or XFZ on this CMnet.
Module generated Alert alarms:
Module Halted:
Alarm ID: A250
One or more GFBs stopped:
Alarm ID: A253
Manual I/O Locked (for each GFB):
Alarm ID: A1
GFB parameter or other error (for each GFB):
Alarm ID: M4

LGM Module Driver Parameters

The SiteGate-232 is properly configured by altering the module driver parameter page values. The
parameters are used for defining dialing information, modem control, and CMnet characteristics.
BACnet Device Parameters
Use default device object name? This is a character string that represents the unique internetwork-
wide object. The minimum length of the string is one character. The default string of this parameter is
LGxCMy.
x parent LANgate LG address in decimal
y Portal's CM address in decimal
Use default object ID? This is a numeric code that is used to identify the object. Choose NO to enter a
custom object ID (range: 1-4194303). Otherwise a default string of 240zzz will be assigned.
zzz parent LANgate LG address in decimal plus CMnet address in decimal
APDU Timeout Indicates the amount of time between retransmissions of an APDU requiring
acknowledgement for which no acknowledgement has been received. The default value of this
parameter is 3000 milliseconds.
Number of APDU Retries Indicates the maximum number of times that an APDU is transmitted. The
default value of this property is zero (0).
CMnet Parameters General
Generate dead module alarm after 10 minutes of no communications with a control module. If a
module has not reported its color within this time, the SiteGate-232 will generate a "dead module"
alarm.
Zero compression enabled? YES: Zero compression makes the CMnet more efficient. This parameter
should always be set to YES. It should only be set to NO if there is a need to examine uncompressed
CMnet traffic to diagnose a CMnet problem.
Rev. (08-JULY-98)
Note: the minimum value for this is 5:00.
2:00 (mm:ss) for connection before hanging up.
5:00 (mm:ss) before
1000 msec.
1000 msec.
500
msec.
Enable: YES
Critical: YES
Enable: YES
Critical: YES
Enable: YES
Critical: YES
Enable: YES
Critical: YES
Send RTN: YES
Send RTN: YES
Send RTN: YES
Send RTN: YES
16