Bosch D296 Installation Instructions Manual page 21

Bosch d296; d297 smoke detector
Hide thumbs Also See for D296:
Table of Contents

Advertisement

Long-range Beam Smoke Detectors
Notice!
When performing fine-tune alignment, keep your arms and hands away from the front of the
receiver and out of the beam path.
Notice!
Peak the voltage to ensure a stable and trouble-free detector.
5.
6.
7.
8.
9.
10. Press the receiver's Setup button, located below the P6 and test cable connection as
Figure 6.6: Receiver Setup Button
Notice!
Only press the Setup button if the covers are on both the transmitter and receiver.
Notice!
During this time, do not block the beam or move the units.
Bosch Security Systems, Inc.
The maximum voltage peak reading varies, depending on the distance between the
transmitter and receiver. The acceptable peak voltage range is from 0.50 V to 5.00 V. The
voltage at the receiver is greater at shorter distances.
Make a note of the alignment voltage. It might be helpful if you need to troubleshoot at
another time.
After completing the fine-tune alignment, remove the test cable.
Replace and secure the receiver's cover.
Check the status of the receiver's green LED to ensure it is still flashing.
With the meter still connected to the test cable, reinstall this cable to P6. Route the test
cable through the opening in the cover (white lead towards center of the receiver).
At this point, you can perform an Alarm Test. Connect the D1005's white and black wires.
Reset the receiver by temporarily removing power.
indicated in the following figure.
1 LEDs
A 1-min to 2-min automatic internal setup process begins. This setup ends in a reference
voltage that is used to measure beam blockages.
The red and yellow LEDs turn off and the green LED turns steadily on. After some voltage
fluctuations, the meter sets to 5.0 VDC.
Installation Instructions
2 Setup button
2014.01 | 06 | F.01U.068.899
Notices | en
21