Long-range Beam Smoke Detectors
Figure 5.3: Transmitter and Receiver Placement
* maximum spacing between adjacent systems is 60 ft (16.3 m)
Notice!
When two or more adjacent detectors are installed in the same area, alternate the transmitter
and receiver locations. If the transmitter and receiver are not alternated, ensure the spacing
between the detectors is 1/5th the distance from the transmitter to the receiver.
6

Setup

Before performing a setup, ensure all connections are made and secure. Then, apply power to
the transmitter and receiver.
1.
Bosch Security Systems, Inc.
1 Receiver
2 FACP
3 Transmitter
To allow the transmitter to power up while the cover is off, press the transmitter's Aim
Mode button located above the green LED as indicated in the following figure.
Installation Instructions
4 EOL resistor
5 Minimum spacing = 1/10 x distance
6 Minimum spacing = 1/5 x distance