2-11. EXPANSION VALVE CONTROL/LEV CONTROL (MUZ-GC/FD/GE HC35)
(1) Outline of LEV control
The LEV basic control is setting of LEV opening degree to the standard opening degrees set for each operational fre-
quency of the compressor. However, when any change in indoor/outdoor temperatures or other factors cause air condi-
tioning load fluctuation, the LEV control also works to correct LEV opening degree based on discharge temperature (Shell
temperature) of the compressor, developing the unit's performance.
Control range
Actuating speed
Opening degree adjustment
Unit OFF
Remote controller ON
During 1 to 15 minutes after compressor starts
More than about 15 minutes have passed since com-
pressor start-up
Thermostat OFF
Thermostat ON
Defrosting in HEAT mode
(2) Time chart
Air conditioner ON
Positioning
Opening degree is
corrected according
to discharge
temperature.
Standard
(Refer to (3))
opening
degree
About 15 minutes
ON
Minimum : 54 pulse
Maximum : 500 pulse
Open: 40 pulse/second
Close: 90 pulse/second.
LEV opening degree is always adjusted in opening direction.
(When reducing the opening degree, LEV is once over-closed,
and then adjusted to the proper degree by opening.
LEV remains at maximum opening degree. (LEV is reached
maximum opening degree approximate in 15 minutes after
compressor stops)
LEV is positioned. (First LEV is full closed at zero pulse and
then positioned.)
LEV is fixed to standard opening degree according to opera-
tional frequency of compressor.
LEV opening degree is corrected to get target discharge tem-
perature of compressor.
(For lower discharge temperature than target temperature,
LEV is corrected in closing direction.)
(For higher discharge temperature than target temperature,
LEV is corrected in opening direction.)
It may take more than 30 minutes to reach target tempera-
ture, depending on operating conditions.
LEV is adjusted to exclusive opening degree for thermostat
OFF.
LEV is controlled in the same way as that after the compressor
has started up.
LEV is adjusted to open 500 pulse.
Air conditioner OFF
(thermostat off)
Commanded
to open
Time
OFF Time
22