Electric Characteristics - Daikin FTK09NMVJU Engineering Data

Cooling only / heat pump - seer 18 models
Hide thumbs Also See for FTK09NMVJU:
Table of Contents

Advertisement

EDUS041502

10. Electric Characteristics

Unit Combination
Indoor Unit
Outdoor Unit
FTK09NMVJU
RK09NMVJU
FTK12NMVJU
RK12NMVJU
FTK18NMVJU
RK18NMVJU
FTK24NMVJU
RK24NMVJU
FTX09NMVJU
RX09NMVJU
FTX12NMVJU
RX12NMVJU
FTX18NMVJU
RX18NMVJU
FTX24NMVJU
RX24NMVJU
Symbols:
MCA
: Min. circuit amps (A)
MFA
: Max. fuse amps (A)
RHz
: Rated operating frequency (Hz)
RLA
: Rated load amps (A)
OFM
: Outdoor fan motor
IFM
: Indoor fan motor
W
: Fan motor rated output (W)
FLA
: Full load amps (A)
Split Type Air Conditioners FTK(X)-N Series
Power Supply
Hz - Volts
Voltage Range
60 - 208
Min. 187 V
Max. 253 V
60 - 230
60 - 208
Min. 187 V
Max. 253 V
60 - 230
60 - 208
Min. 187 V
Max. 253 V
60 - 230
60 - 208
Min. 187 V
Max. 253 V
60 - 230
60 - 208
Min. 187 V
Max. 253 V
60 - 230
60 - 208
Min. 187 V
Max. 253 V
60 - 230
60 - 208
Min. 187 V
Max. 253 V
60 - 230
60 - 208
Min. 187 V
Max. 253 V
60 - 230
Compressor
MCA
MFA
RHz
RLA
12.1
15
64
12.2
15
88
18.3
20
70
10.0
18.3
20
92
12.0
12.1
15
88
12.2
15
96
18.3
20
90
10.8
18.3
20
96
12.0
Notes:
1. RHz is the max frequency that comes in cooling operation and
heating operation.
2. RLA is the max current that comes in cooling operation and heating
operation.
3. Maximum allowable voltage variation between phases is 2%.
4. Select wire size based on the larger value of MCA.
5. Instead of a fuse, use a circuit breaker.
6. Be sure to install a ground leak detector.
(This unit uses an inverter, which means that a ground leak detector
capable of handling high harmonics must be used in order to prevent
malfunctioning of the ground leak detector.)
Electric Characteristics
OFM
IFM
W
FLA
W
6.8
14
0.13
21
7.5
18
0.15
28
69
0.45
46
58
0.38
46
8.5
14
0.13
21
8.5
18
0.15
28
69
0.45
46
58
0.38
46
FLA
0.20
0.23
0.30
0.30
0.20
0.23
0.30
0.30
3D093165
53

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents