Start Up In Normal Mode - X-TREME 6kVA User & Installation Manual

Online ups
Table of Contents

Advertisement

TX90 6kVA & 10kVA User's Manual

Start Up in Normal Mode

• Open the terminal block cover on the rear panel. Before starting the installation make sure the wiring is
connected properly.
• Make sure the utility input breaker and the UPS' input breaker are in the "Off" position.
• Switch on the utility input breaker on the distribution panel and the UPS input breaker. Then the UPS will
start up. Green LEDs and show that the Utility and Bypass inputs are normal. UPS will display first figure
A1 and then figure B.
A1
B
• The UPS is now in Bypass Mode. It will proceed to self-test automatically. If no abnormal message appears
then the pre-startup of the UPS was successful and the charger begins to charge the batteries
• Press the UPS On switch
changes from figure B to figure C.
C
• The UPS is in self-test mode again. The LCD display will change from figure C to figure D, and the UPS will
remain in battery mode for approximately four seconds. Then the display will change from figure E1 to
figure F if the self-test was successful.
D
"test"
Xtreme Power Conversion Corporation
for approximately three seconds. The Buzzer sounds twice and the LCD display
Uninterruptible Power Supply
Page 15

Advertisement

Table of Contents
loading

This manual is also suitable for:

10kvaTx9010kvaTx90 6kva

Table of Contents