17. Alternate materials worksheet
How to determine if alternate floor protection materials are acceptable:
All floor protection must be non-combustible (i.e., metals, brick, stone, mineral fiber boards, etc.). Any organic materials (i.e., plastics, wood paper
products, etc.) are combustible and must not be used. The floor protection specified includes some form of thermal designation such as R-value
(thermal resistance) or k-factor (thermal conductivity).
PROCEDURE:
1. Convert specification to R-value:
R-value given - no conversion needed.
k-factor is given with a required thickness (T) in inches:
2. Determine the R-value of the proposed alternate floor protector.
i. Use the formula in step (1) to convert values not expressed as "R".
ii. For multiple layers, add R-values of each layer to determine overall R-value.
3. If the overall R-value of the system is greater than the R-value of the specified floor protector, the alternate is acceptable.
EXAMPLE: The specified floor protector should be 3/4 inch thick material with a k-factor of 0.84. The proposed alternate is 4" brick with an r-factor
of 0.2 over 1/8" mineral board with a k-factor of 0.29.
Step (a): Use formula above to convert specification to R-value.
Step (b): Calculate R of proposed system.
Step (c): Compare proposed system R total of 1.231 to specified R of 0.893. Since proposed system R total is greater than required, the system
is acceptable.
2
o
(ft
)(hr)(
DEFINITIONS
R =
Btu
18. Position the Hearth Extension
Position and secure the hearth extension over the
protective metal strips that have been placed partially
under the fireplace front. These strips should be
protruding approximately 2" from under the fireplace
front and 2" on both sides of the fireplace opening.
See Figure 13A on page 13. Seal the crack between
the hearth extension and fireplace with a bead of
noncombustible sealant. See Figure 18A. Apply a
noncombustible finishing material of your choice to the
hearth extension.
NOTE: SEE PAGE 5 "CLEARANCES TO COM-
BUSTILES, HEARTH EXTENSIONS / FLOOR PROTEC-
TION" FOR CLEARANCES REQUIRED FOR DIFFER-
ENT HEARTH EXTENSIONS INSTALLATIONS. THE
CLEARANCES MUST BE STRICTLY ADHERED TO.
WARNING!
Hearth extensions are to be installed only as illustrated to
prevent high temperatures from occurring on concealed
combustible materials. Hearth sealing strips prevent
burning or hot particles from inadvertently falling directly
on combustible surfaces in the event the building should
settle and disturb the original construction.
480-1091
R =
4" brick of r = 0.2, therefore:
R
= 0.2 x 4 = 0.431
brick
R
= R
total
brick
F)
Btu(in)
= K x 12
k =
2
o
ft
(hr)(
F)
K-factor is given with a required thickness (T) in inches:
1
x T
r-factor is given with a required thickness (T) in inches: R = r x T
k
1
1
x 0.75 = 0.893
=
R =
x T
.84
k
1/8" mineral board of k = 0.29, therefore:
R
=
mineral board
+ R
= 0.8 + 0.431 = 1.231
mineral board
Btu(ft)
2
r = (ft
)(hr)(
K =
2
o
ft
(hr)(
F)
(Btu)(in)
1
R =
x T
k
Seal with non-
combustible sealant
Figure 18A - Position the Hearth Extension
18
1
x 0.125 = 0.431
0.29
1
o
F)
=
k
1
x T
R =
K x 12
1
x T
R =
K x 12
4-03