STEP 5 -- ELECTRICAL -- Circuit Sizing and Wire Routing
In the U.S.A., wiring must conform with current local codes
and the current National Electric Code (NEC). In Canada,
wiring must conform with current local codes and the cur­
rent Canadian Electrical Code (CEC).
Refer to the furnace or air handler installation instructions
for additional wiring application diagrams and refer to unit
nameplate for minimum circuit ampacity and maximum
overcurrent protection size.
24VAC TRANSFORMER
Use the transformer provided with the furnace or air han­
dler for low‐voltage control power (24VAC - 40 VA mini­
mum)
WARNING
Electrical Hazard
High Voltage
Wait 5 Minutes
Electrical components may hold charge.
Do not remove this panel or service this
area for 5 minutes after the power has
been removed.
SIZE CIRCUIT AND INSTALL DISCONNECT
1
SWITCH
Refer to the unit nameplate for minimum circuit
ampacity, and maximum fuse or circuit breaker size
(HACR per NEC). Install power wiring and properly
sized disconnect switch.
SERVICE
DISCONNECT
SWITCH
NOTE — Units are approved for use only with copper
conductors. Ground unit at disconnect switch or
connect to an earth ground.
ELECTROSTATIC
DISCHARGE
(ESD)
Precautions and
Procedures
2

INSTALL THERMOSTAT

Install room thermostat (ordered separately) on an
inside wall in the center of the conditioned area and
5 feet (1.5m) from the floor. The thermostat should
not be installed on an outside wall or where it can be
affected by sunlight or drafts.
THERMOSTAT
5 FEET
(1.5M)
NOTE — 24VAC, Class II circuit connections are made
in the control box.
FIGURE 9
Page 12
CAUTION
Electrostatic discharge can affect
electronic components. Take care
during unit installation and service to
protect the unit's electronic controls.
Precautions will help to avoid control
exposure to electrostatic discharge by
putting the unit, the control and the
technician at the same electrostatic
potential. Touch hand and all tools on an
unpainted
unit
surface
performing any service procedure to
neutralize electrostatic charge.
before

Advertisement

Table of Contents
loading

Table of Contents