Fujitsu AS*G24LFCA Service Instruction page 72

Room air conditioner wall mounted type inverter
Hide thumbs Also See for AS*G24LFCA:
Table of Contents

Advertisement

Outdoor Unit High Pressure Value and Outdoor Total Electric Current Curve (Heating)
Model Name : AS*G30LFCA
[Condition]
Ambient
Indoor 15, 20, 23 C, Outdoor 2, 7, 12 C
temperature
Refrigerant
Standard amount
amount
Piping
7.5m (Height difference 1m)
length
Power
50Hz - 240V
voltage
Operation
TEST mode (Heating), Hi Fan, One step up from lower direction, Front air flow
condition
Measuring
outdoor unit overall current with the current clamp meter at Power Cable.
method
Caution
Start operation with the condition of the Indoor Unit air filter clean.
[Constant Frequency Operation Method (Test mode)]
1. Operate on Heating mode, and press TEST button of remote control.
2. Operate continuously for 30 minutes. (After 60 minutes of operation, Test mode is released automatically.)
(1) Indoor/Outdoor Temperature - Outdoor High Pressure Curve
AS*G30LFCA
3.4
23 C
3.3
Indoor ambient
20 C
temperature[ C]
3.2
15 C
3.1
3.0
2.9
2.8
2.7
2.6
2.5
2.4
0
2
4
6
Outdoor ambient temperature [ C]
(2) Indoor/Outdoor Temperature - Outdoor Total Electric Current Curve
AS*G30LFCA
14.0
13.5
23 C
Indoor ambient
13.0
20 C
temperature[ C]
15 C
12.5
12.0
11.5
11.0
10.5
10.0
9.5
9.0
0
2
4
Outdoor ambient temperature [ C]
8
10
12
[50Hz-240V]
6
8
10
12
[50Hz-240V]
14
14
03-08