Trouble shooting 7
INDOOR UNIT Error Method:
Indoor Heat Ex. Thermistor Error
Detective Actuators:
Indoor unit Controller PCB
Heat exchanger (MID) Thermistor
Forecast of Cause : 1. Connector failure connection 2. Thermistor failure 3. Controller PCB failuer
Check Point 1 : Check connection of Connector
Check if connector is loose or removed
Check erroneous connection
Check if thermistor cable is open
>>Reset Power when reinstalling due to removed connector or incorrect wiring.
OK
Check Point 2 : Remove connector and check Thermistor resistance value
Thermistor Characteristics (Rough value)
Temperature
(°C )
Resistance value (k )
Temperature
(°C )
Resistance value (k )
If Thermistor is either open or shorted, replace it and reset the power.
OK
Check Point 3 : Check voltage of Controller PCB (DC5.0V)
Make sure circuit diagram of each indoor unit and check terminal voltage at Thermistor (DC5.0V)
RED
BLACK
1
1
1
CN3
2
2
2
WHITE
BLACK
3
3
BLACK
1
CN1
BLACK
2
If the voltage does not appear, replace Controller PCB and execute the check operation again.
Indicate or Display:
Refer to error code table.
Detective details:
Heat exchanger (MID) thermistor is open or short is detected always.
0
5
10
176
134
103
40
45
50
25.6
20.9
17.1
H/E Thermistor
Room Temp. Thermistor
15
20
25
80.3
62.9
49.7
60
70
80
11.6
8.12
5.78
02-09
30
35
39.6
31.7
90
100
4.19
3.09
DC