Perforated Face Supply - Rotating Vane Method
1. Hood set up.
If the make-up air unit has a temperature control, it
should be used to keep the supply air at the desired
room discharge air temperature.
2. Measure velocities.
Divide the perforated face panel into a grid of equal
areas, each approximately 4 in. (101.6 mm) square.
Measure the velocity at the center of each grid
area. A digital 2.75 in. (69.85 mm) rotating vane
anemometer or equivalent is suggested. The center
of the anemometer should be held tight to the face
of the panel and parallel to the filter. Both squareness
and distance are important for accuracy. Calculate
the average velocity of the panel.
3. Measure the length and height of the perforated face
panel.
Example: Face supply hood with three 28 inch (.711 m) perforated panels
Measured velocities in ft/min. for one perforated panel
Average Velocity
=
=
(Imperial)
=
(Metric)
Measure length and height. 28 inches (.711 m) long perforated panel by 16 inches (.406 m) high
Volume for one panel = Conversion Factor x
=
(Imperial)
=
(Metric)
Total system volume =
=
(Imperial)
=
(Metric)
22
Kitchen Hoods • Type I and Type II
Sum of Velocity Readings
Number of Readings
260 + 250 + ... + 265 + 260
28
4755 + 4572 + ... + 4846 + 4755
28
Average Velocity
0.005
x
0.72
x
(Panel 1 Volume)
+
(Panel 2 Volume)
606.4
+
1029
+
4. Calculate the perforated face panel volume using the
following formula:
CFM = avg. velocity x length (in.) x height (in.) x 0.005
m/hr = avg. velocity x length (m) x height (m) x 0.72
5. Calculate the system's volume by repeating the
process for the remaining panels and adding the
individual panel volumes together.
Filter Readings (ft/min.)
260
250
270
275
290
285
285
275
4755
4572
4938
5029
5304
5212
5212
5029
= 270.7 ft/min.
= 4951 m/hr
x
Length
270.7 ft/min.
x
28
4951 m/hr
x
.711
+
(Panel 3 Volume)
614.3
+
1044
+
255
260
250
255
270
280
265
265
280
280
275
290
280
260
270
265
Filter Readings (m/hr)
4663
4755
4572
4663
4938
5121
4846
4846
5121
5121
5029
5304
5121
4755
4938
4846
x Height
x
16
=
606.4 cfm
x
.406
= 1029 m
593.8
=
1814.5 cfm
1009
=
3082 m
265
270
295
260
4846
4938
5395
4755
3
/hr
3
/hr